Electrical Data - Carrier 50KQA Product Data

Console water source heat pumps
Table of Contents

Advertisement

Electrical data

50KQA,KQD
VOLTAGE
115-1-60
007
208/230-1-60
265-1-60
115-1-60
009
208/230-1-60
265-1-60
115-1-60
012
208/230-1-60
265-1-60
208/230-1-60
015
265-1-60
208/230-1-60
019
265-1-60
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
— Rated Load Amps
RLA
RATED
VOLTAGE
MIN/MAX
104/126
197/254
239/292
104/126
197/254
239/292
104/126
197/254
239/292
197/254
239/292
197/254
239/292
50KQA,KQD
COMPRESSOR
MOTOR
RLA
LRA
6.2
36.2
3.0
17.7
2.7
14.8
7.4
44.0
3.8
20.0
3.3
18.6
9.7
54.0
4.8
26.3
4.2
28.0
6.4
38.0
5.4
32.0
7.6
45.0
6.3
32.0
FAN
TOTAL
MIN
UNIT
CIRCUIT
FLA
FLA
AMP
0.50
6.9
8.5
0.33
3.4
4.2
0.35
3.3
4.0
0.50
8.8
10.9
0.33
4.8
6.0
0.35
3.7
4.5
1.28
11.5
14.0
0.52
5.4
6.6
0.43
4.8
5.9
0.52
7.5
9.3
0.43
5.9
7.3
1.10
9.4
11.5
0.83
7.2
8.8
MAX
FUSE/
HACR
15
15
15
15
15
15
20
15
15
15
15
15
15
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50kqd

Table of Contents