Table 5 - Orion Power Systems SCR2 User Manual

10kva online ups
Table of Contents

Advertisement

Table 5

Troubleshooting guide (continued)
P
o r
b
e l
m
Fault indicator and diagnostic
indicators B and D are
illuminated.
Fault indicator and diagnostic
indicators C and E are
illuminated.
Fault indicator and diagnostic
indicators D and E are
illuminated.
AC Input indicator is On &
diagnostic indicators A, C and
E are illuminated.
AC Input indicator is On &
Battery indicator is flashing.
Bypass indicator is flashing.
C
a
u
s
e
UPS output is OFF from a
previous REPO command.
REPO is no longer activated.
UPS shutdown due to a
command from the
communications port(s).
UPS charger fault.
On Internal Bypass to notify
user to rotate manual
maintenance bypass switch
to Bypass position.
Battery source is not
available; continuous horn.
Bypass voltage is present,
but is disabled for use
because the voltage or
frequency is outside
acceptable limits.
UPS is OFF due to previous REPO (REPO is no longer
activated). Once utility power is restored, press the OFF
button twice within four seconds (to clear the alarm), then
press the ON button to start UPS (Auto-restart is NOT
possible).
Your UPS has received a signal or command from the
attached computer. If this was inadvertent, ensure the
communication cable used is correct for your system. For
assistance, contact your local dealer, sales
representative or Technical Support Services.
UPS requires service. Contact your local dealer,
sales Representative or Technical Support Services.
Rotate manual bypass switch to the Bypass position, then
follow the instructions for replacing the UPS power module
(see 12.2 - UPS Power Module Replacement).
Check battery connections, completely power down and
restart UPS.
NOTE: If the battery circuit opens while the UPS is
running, it will be detected when the next battery test is
performed.
The AC input powers the PFC input and serves as the
bypass source. If the AC is present but the voltage or
frequency exceeds the acceptable range for safe
operation with a load, the bypass will be disabled and this
indicator will flash, indicating that the bypass is
unavailable.
32
Troubleshooting
S
l o
t u
o i
n

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents