7

WIRING DIAGRAM

PCA-RP71HAQ
[LEGEND]
SYMBOL
NAME
P. B
INDOOR POWER BOARD
I. B
INDOOR CONTROLLER BOARD
FUSE
FUSE (T6.3AL250V)
CN2L
CONNECTOR (LOSSNAY)
CN32
CONNECTOR (REMOTE SWITCH)
CN41
CONNECTOR (HA TERMINAL-A)
CN51
CONNECTOR (CENTRALLY CONTROLL)
LED1
POWER SUPPLY (I. B)
LED2
POWER SUPPLY (R. B)
LED3
TRANSMISSION (INDOOR-OUTDOOR)
X1
RELAY (DEW PREVENTION HEATER)
X4
RELAY (FAN MOTOR)
X5
RELAY (FAN MOTOR)
X6
RELAY (FAN MOTOR)
SW1
SWITCH (MODEL SELECTION) See Table 1.
SW2
SWITCH (CAPACITY CODE) See Table 2.
SWE
SWITCH (EMERGENCY OPERATION)
MF1
M
1~
6 5 4 3 2 1
ORN
6 5 4 3 2 1
BRN
C1
C2
RED
GRY
I.B
FAN
WHT )
(
1 3 5
7
X6 X5 X4
SWE
SW2
SW1
ON
OFF
Refer to tables 1
and 2 for service PCB.
Table 1
SW1
Service board
1 2 3 4 5
ON
OFF
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3. Symbols used in wiring diagram above are,
1 When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1.
2 For power supply system of this unit, refer to the caution label located near this diagram.
PCA-RP125HAQ
SYMBOL
MF1, MF2
FAN MOTOR
C1, C2
CAPACITOR (FAN MOTOR
H2
DEW PREVENTION HEATER
TB2
TERMINAL BLOCK (INDOOR UNIT
POWER (OPTION PARTS))
TB4
TERMINAL BLOCK (INDOOR/OUTDOOR
CONNECTING LINE)
TB5,TB6
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
TH1
ROOM TEMP.THERMISTOR
(0°C/15kΩ, 25°C/5.4kΩ DETECT
TH2
PIPE TEMP.THERMISTOR/LIQUID
(0°C/15kΩ, 25°C/5.4kΩ DETECT
TH5
COND./ EVA.TEMP.THERMISTOR
(0°C/15kΩ, 25°C/5.4kΩ DETECT
R. B
WIRED REMOTE CONTROLLER BOARD
For PCA-RP125HAQ
MF2
M
1~
P.B
CNSK
( RED)
1
H2
DC13.1V
3
D.HEATER
POWER
POWER
CNC
CNDK
1 3
CND
3
1
( RED)
( RED)
( ORN)
X1
LED3
LED2
LED1
Table 2
SW2
MODELS
Service board
MODELS
1 2 3 4 5
PCA-RP71HAQ
ON
PCA-RP125HAQ
OFF
The black square (
) indicates a switch position.
: Connector,
Check code
NAME
P1
)
P2
P6
P8
P9
E0 - E5
E6 - EF
Fb
)
U* , F*
- - - -
)
FFFF
)
CN2S
( WHT)
1
2
TB4
YLW
S1
S1
ORN
S2
S2
ORN
S3
S3
BRN
1 3
1
3
1
2
INDOOR/OUTDOOR
POWER
COMMUNICATION
CN2D ( WHT)
CN3C ( BLU)
CN41
CN2L
CN51
CN32
4
1
2
1
5
1
1
3
INTAKE
LIQUID
PIPE
REMOCON
CN20
CN21
CN29
CN22
( RED)
( WHT)
( BLK)
( BLU)
1 2
1 2
1 2
1 2
2
2
TB5
2
1
2
1
3
1
2
TH1
TH2
TH5
Service board
1 2 3 4 5
ON
OFF
: Terminal (block).
13
13
Symptom
Abnormality of room temperature thermistor
Abnormality of pipe temperature thermistor/Liquid
Freezing/overheating protection is working.
Abnormality of pipe temperature
Abnormality of pipe temperature thermistor/Cond.Eva.
Abnormality of the signal transmission between remote
controller and indoor unit
Abnormality of the signal transmission between indoor unit
and outdoor unit
Abnormality of indoor controller board
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
No trouble generated in the past.
No corresponding unit
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
TO
1 (Fig.1)
OUTDOOR
TB2
UNIT
RED
L
BLU
N
GRN/YLW
YLW
TB4
ORN
S1
S1
ORN
S2
S2
BRN
S3
S3
I.B
1 3
1 3
POWER
INDOOR/OUTDOOR
CND
COMMUNICATION
(ORN)
CN3C
(OPTION PARTS)
(BLU)
R.B
1
TB6
TRANSMISSION WIRES DC12V
2
(
TH1)
TH2)
(
(
TH5)
POWER
SUPPLY
~(1PHASE)
230V 50Hz
TO
OUTDOOR
UNIT

Hide quick links: