[Procedure example]
Manual address setup procedure
While the operation stops, change the setup.
(Stop the operation of the unit.)
3
-2,
4
-2,
5
-2
7
1
2,6
1
Push
+
+
buttons simultaneously
for 4 seconds or more. After a while, the
display part flashes as shown below.
Check the displayed CODE No. is [10].
When the CODE No. is other than [10], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the
remote controller is not accepted for approx.
1 minute.)
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
(* Display changes according to the
model No. of indoor unit.)
2
Every time
button is pushed, the
indoor UNIT No. in the group control is
displayed in order. Select the indoor unit of
which setup is changed.
In this time, the position of the indoor unit of which
setup is changed can be confirmed because fan
of the selected indoor unit operate.
3
1) Specify CODE No. [12] with TEMP.
buttons.
(CODE No. [12]: Line address)
2) Change the line address from [3] to [2] with
TIME
/
buttons.
29-EN
3) Push
button.
In this time, the setup finishes when the
display changes from flashing to lighting.
Indoor unit No. before setup change is displayed.
7
3
-1,
4
-1,
5
-1,
6
3
-3,
4
4
-3,
5
1) Specify CODE No. [13] with TEMP.
-3,
buttons.
(CODE No. [13]: Indoor address)
2) Change the indoor address from [3] to [2]
TIME
/
buttons.
3) Push
button.
In this time, the setup finishes when the
display changes from flashing to lighting.
Indoor unit No. before setup change is displayed.
5
1) Specify CODE No. [14] TEMP.
buttons.
(CODE No. [14]: Group address)
2) Change the SET DATA from [0001] to [0002]
TIME
/
buttons.
(SET DATA [Header unit: 0001] [Follower
unit: 0002])
3) Push
button.
In this time, the setup finishes when the
display changes from flashing to lighting.
Indoor unit No. before setup change is displayed.
/
– 15 –
6
If there is other indoor unit to be changed,
repeat procedure
setup.
When the above setup has finished, push
to select the indoor UNIT No. before change of
setup, specify CODE No. [12], [13], [14] in order
with TEMP.
/
changed contents.
Address change check Before change:
[3-3-1] → After change: [2-2-2]
Pushing
button clears the contents of which
setup was changed.
(In this case, procedure from
/
Indoor UNIT No. before setup change is displayed.
7
After check of the changed contents, push
button. (setup is determined.) When
button is pushed, the display disappears
and the status becomes the usual stop
status. (when
/
operation from the remote controller is not
accepted for approx. 1 minute.)
*
If the operation from the remote controller is
not accepted even 1 minute or more passed
after pushing
address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup change
from the Procedure
To recognize the position of the
2
5
corresponding indoor unit though the
to
to change the
indoor UNIT No. is known
Check the position during operation stop.
(Stop operation of the set.)
buttons, and then check the
2
is repeated.)
1,3
1
Push
4 seconds or more.
After a while, the display part flashes and the
display appears as shown below.
In this time, the position can be checked
because fan of the indoor unit operate.
For the group control, the indoor UNIT No. is
displayed as [
units in the group control operate.
Check the displayed CODE No. is [01].
When the CODE No. is other than [01], push
button to erase the display and repeat procedure
from the first step.
(After pushing
controller is not accepted for approx. 1 minute.)
button is pushed the
(* Display changes according to the
model No. of indoor unit.)
2
In the group control, every time
button is pushed, the indoor UNIT No. in
button, it is considered that the
the group control is displayed in order.
In this time, the position of the indoor unit can be
confirmed because only fan of the selected indoor
unit operate.
(For a group control, No. of the firstly displayed
1
.
indoor unit becomes the header unit.)
3
After confirmation, push
the mode to the usual mode.
When
and the status becomes the usual stop status.
(When
remote controller is not accepted for approx.
1 minute.)
1
2
+
buttons simultaneously for
] and fans of all the indoor
button, operation of the remote
button to return
button is pushed, the display disappears
button is pushed the operation from the
30-EN