Installation method (continued)
(2) Confirm that the pulse input switch (SW2-2) is set to "OFF".
(Set to "OFF" at time of shipment.)
Remote controller
(PZ-60DR-E or PZ-41SLB-E)
External device
Power supply
Operating switch for
external device
When using Mitsubishi Mr. Slim air conditioner with MA
Remote controller
Connect the interlocking cable connector side to CN2L on the
circuit board for the indoor Mr. Slim unit, then connect the lead
wire side to the 1 and 2 of the input terminal block (TM2) for the
Lossnay external controller input. (No polarity)
• Always separate the power supply cable and the Slim-Lossnay
connection cable by 5 cm or more to prevent the unit from
malfunctioning.
• The Slim-Lossnay connection cable is 0.25 m long. When
wiring, extend it as far as necessary.
Lossnay
External controller input (TM2)
Within 500 m
Note
The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E)
cannot be used with this system.
Use MA remote controller of Mr. Slim for switching
Lossnay ON/OFF or the fan speed.
The ventilation mode is "automatic ventilation".
The Slim-Lossnay connection cable may be extended to a
maximum length of 500m. (Extension cable specifications
are as detailed below)
Ensure that all connections are secure and that the
appropriate insulation is provided.
Use extension cable sheathed PVC cable or cable 0.5 mm
to 1.0 mm
.
2
When the external device has a charged operating signal
of 12 VDC or 24 VDC
• Connect the operating signal (wire) from the external device
via the remote output to 1 and 2 on the external control input
terminal block (TM2). (No polarity)
Lossnay External control input (TM2)
Overall connection extension length
(Follow the operation manual for the external equipment.)
When the external device has an uncharged a-contact signal
• Connect the operating signal (wire) from the external device
via the remote output to 1 and 3 on the external control input
terminal block (TM2).
18
Lossnay
Power supply
Slim-Lossnay connection cable
(Enclosed accessory)
CN2L
White
Mr. Slim (Indoor unit)
Red
Printed circuit board
0.5 mm
2
to 1 mm
2
sheathed PVC cable
External device
12 or 24 VDC
Lossnay External controller input (TM2)
CAUTION
If an optocoupler or any other type of polar coupler is used at
the uncharged a-contact, connect the positive side to 3 and
the negative side to 1.
3
When interlocking with a pulse output device
(1) Move the pulse input switch [SW2-2] to the ON position.
(Refer to function settings
(2) Connect the pulse output device (i.e., building management
system) to the external control input terminal block [TM2].
• A pulse width of at least 200 msec will be needed.
• When using PZ-60DR-E, it can be set also from the remote controller.
Connecting methods vary depending on the types of pulse signal
Refer to Section
2
"When the external device has a charged
operation signal of 12 VDC or 24 VDC" or "When the external
device has an uncharged a-contact signal".
1
SW2
4
When operating multiple Lossnay units
(1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2 to
Unit 3 and so on up to a maximum of 15 units using a transmission
cable (PVC insulated PVC jacketed and either between ø0.65 and
ø1.2, or between 0.3 mm
(2) Change the setting on the main/sub switch (SW1) on the
second and subsequent Lossnay units to "Sub".
Remote controller
(PZ-60DR-E or PZ-41SLB-E)
Power supply
Power
External
supply
Operating switch
device
for external device
2
Power
supply
Power
supply
CAUTION
Don't tighten screws of terminal block with a torque larger
than 0.5 Nm. It could damage the PCB.
Note
Up to four 0.3 mm
be connected to one input terminal.
For other types of wire, up to two can be connected.
The operation signal and pulse signal can be connected to
the external device of the main Lossnay only.
Connect the power to each respective Lossnay unit.
0.5 mm
to 1 mm
sheathed PVC cable
2
2
External device
Uncharge a-contact
Within 500 m
1
"Settings for pulse input".)
ON
2
3
4
5
6
7
8
9 10
ON
OFF
and 1.25 mm
in cross section).
2
2
Lossnay (Main)
Main/Sub selection switch
(SW1)
Main
Sub
(Factory setting: main)
First
Lossnay (Sub)
Lossnay
TM4
1
2
Second
Lossnay
TM4
1
2
Lossnay (Sub)
Transmission cable
MAX 15 units
2
stranded wires or ø 0.65 PVC wires can
Connect
to remote
controller
(PZ-60DR-E)
Connect
to third
Lossnay