Menu Dial; How To Use The Control Panel; Basic Functions - Worcester Greenstore 6kW Instruction Manual

Hide thumbs Also See for Greenstore 6kW:
Table of Contents

Advertisement

Menu dial

How to use the control panel

Example
Basic functions (Customer level 1)
Compressor temperature T6 (GT6)
Possible cause 1: The working temperature of the compressor is
Possible cause 2: Intermittent temperature rise due to abnormal
Reg 637
K1
040622 16:08:15 Tu
Heat
Info
Menu
Low pressure switch (LP)
Possible cause 1: Air in the heat collector system.
Reg 637
K1
040622 16:08:15 Tu
Heat
Info
Menu
Possible cause 2: The filter on the collector circuit is blocked.
Possible cause 3: Lack of refrigerant in the refrigerant circuit.
Heat. +/-
0
5,0
10
Return
Adjust
Possible cause 4: The heat transfer fluid pump has stopped or is
Possible cause 5: Ice formation in the evaporator due to a lack
Reg 637
K1
040622 16:08:15 Tu
Heat
Info
Menu
Possible cause 6: Faulty expansion valve (the alarm appears in
too high.
operating conditions.
set at too low a speed.
of anti-freeze in the heat collector circuit.
time periods of 3-4 weeks).
Alarm
(GT6)
Compressor superheat
040622 16:08:15
Info
Ackn.
Alarm
(LP)
Low pressure switch
040622 16:08:15
Info
Ackn.