10.2 Diagnosis and Solution

10.2.1 E0(EEPROM parameter error) error diagnosis and solution
Circuit or software error on indoor PCB
10.2.2 E1(indoor / outdoor units communication protection) error diagnosis and solution
Disconnect the power supply, after 1 minute,
connect the power supply , turn on the unit with
remote controller
Does the unit work normally?
Check the wiring between
indoor and outdoor unit. Is
the connection of L, N, S and
GND good?
Is the GND connection on
outdoor PCB good?
Is the LED4(red) on
outdoor PCB bright and
LED1(yellow) blinking?
The power supply for
outdoor PCB is fail. Check
the wiring on outdoor PCB
comparing with wiring plate.
Is the connection good?
Correct the connection.
10.2.3 E3(indoor fan speed out of control) diagnosis and solution
Is the indoor fan motor
connector and connection
good?
Is voltage being applied
to the fan motor right?
NO
Yes
No
No
YES
NO
NO
Yes
Yes
NO
Repair the connector and
reconnect
YES
Indoor PCB is defective.
Replace the indoor PCB.
Replace the indoor fan
motor
Replace indoor PCB
Reconnect and retest again
Replace indoor PCB
and repower on. Is
the failure cleared?
Replace outdoor e-box.