Sanyo Big PACi 18 Series Technical Data & Service Manual page 81

Big pack i dc inverter
Table of Contents

Advertisement

1
1-3. Other Component Specifi cations
Outdoor Units SPW-C906VH8
MODEL No.
Power Transformer
Rated
Source
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
Thermistor (Discharge gas sensor): TH5
Resistance
Relay (Comp. Magnetic Contactor)
Coil rated
Contact rating
Coil resistance (at 20°C)
Sol-Control-Valve
Sol-control-valve
Magnetic coil
4 way valve
4 way valve
Electro magnetic coil
Outdoor Unit
VAC, Hz
°C
kΩ
kΩ
VAC
VAC, A
1-76
SPW-C906VH8
KTM-35D-S1, DTN-C532G3H
–10°C: 23.7±5%
–5°C: 18.8±5%
0°C: 15.0±5%
5°C: 12.1±5%
10°C:
9.7±5%
CM-12
60°C: 12.4±5%
70°C:
8.7±5%
75°C:
7.4±5%
80°C:
6.3±5%
85°C:
5.3±5%
UKV-25D18
UKV-U030E, DC 12 V
STF-0712G
STF-01AI518A1, AC 220-240 V, 50Hz / 60Hz
20°C:
6.5±5%
30°C:
4.4±5%
40°C:
3.1±5%
45°C:
2.6±5%
50°C:
2.1±5%
90°C:
4.6±5%
100°C:
3.4±7%
110°C:
2.5±7%
120°C:
1.9±7%
130°C:
1.5±7%