Sanyo Big PACi 18 Series Technical Data & Service Manual page 70

Big pack i dc inverter
Table of Contents

Advertisement

1-2. Major Component Specifi cations
(A) Indoor Units
Concealed-Duct High Static Pressure Type
MODEL No.
Source
Controller P.C.B. Ass'y
Fan (Number...diameter)
Fan motor
Model...Nominal output
Power source
No. of pole...r.p.m. (230V, High)
Coil resistance
(Ambient temperature 20°C)
Safety device
Operating temperature
Run capacitor
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Valve body
Heat exchanger
Coil
Rows...fin pitch
Face area
220 - 230 - 240V, single-phase, 50/60Hz
CR-UXRP71B-B (Microprocessor)
mm
W
220 - 230 - 240V, single-phase, 50Hz
rpm
BRN – WHT : 13.75
WHT – VLT :
VLT
– ORG :
Open °C
Close °C
VAC, µF
Aluminium plate fin / Copper tube
mm
2
m
1-65
SPW-D705H
Centrifugal (2...ø220)
KFC4X-201B5P...180 W
4P... 1,012
ORG – YEL :
4.47
YEL – BLK : 10.33
1.20
BLK – PNK : 12.90
130 ± 5
(115 ± 5)
450 VAC, 7.0 µF
3...2.0
0.540
1
2.21