Appendix D. Reference

Appendix D.1. Driver Scope

This driver has implemented cheetah command #6.0. These messages are produced by a Cheetah device
controller and are consumed by this driver. The driver has no control on the frequency of the messages and thus
cannot guarantee fresh data. In addition the protocol has no method for acknowledging messages so that in the
event of this driver having to discard a corrupt message, the message producer does not know and will not re-
send.

Appendix D.2. Panel Firmware Versions

The driver supports older versions of panel firmware which transmit a shorter version of the Panel Status
command. This shorter version contains only panel data whereas the newer version contains panel, zone & device
data.

Appendix D.3. Storing Panel Data

Panel data is stored in consecutive locations as described in the map below. For additional explanations on the
meaning of each data element contact FIKE directly.
Array Location
Data Category
0
Active Counter (0..65535)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Board Status Indicators (0 or 1)
17
18
19
20
21
22
23
24
Date & Time
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Data stored at this location
Active events in normal state
Active events in Process state
Active events in Trouble state
Active events in Supervisory state
Active events in Drill state
Active events in ? state
Active events in ? state
Active events in ? state
Active events in Abort state
Active events in Pre-Alarm1 state
Active events in Pre-Alarm2 state
Active events in Alarm state
Active events in Pre-Discharge state
Active events in Release state
Active events in Zone Discharge state
Active events in Water Mist state
Alarm silence active 1=yes
Supervisory Silence Active 1=yes
Trouble Silence Active 1=yes
AC Power on Main Board 1=ok
AC Power on Aux Board 1=ok
Walk test Condition 1=on
Ground Fault Condition 1=ok
Ack Condition 1=on
Month
Page 29 of 36