Summary of Contents for FieldServer SlotServer FS-RA-CLX-BAS
Page 1
Toll Free: (888) 509-1970 Fax: (408) 262-2296 Email: support@fieldserver.com Web Site: www.fieldserver.com SlotServer Instruction Manual APPLICABILITY & EFFECTIVITY This manual provides instructions for the following FieldServer products: Description FS-RA-CLX-BAS FS-RA-CLX-FIR FS-RA-CLX-PRO The instructions are effective for the above as of January 2006 Instruction Manual Part Number: T17011 Rev.
About this product ...................... 4 PRE-STARTUP CHECKLIST..................5 2.1. Accessories supplied with the SlotServer..............5 2.2. Third party components (not supplied by FieldServer Technologies) ......5 2.3. Required configuration for the SlotServer..............5 STEPS FOR IMPLEMENTATION OF A SLOTSERVER PROJECT ....... 6 3.1.
Page 3
Appendix A.6. Rules for Naming Logix driver Data Arrays ..........31 APPENDIX B. TROUBLESHOOTING TIPS ................33 Appendix B.1. Things to check when communications fail..........33 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
SlotServer Module ordered, supplementary driver manuals are provided for information on how to configure the third party protocols residing in the SlotServer. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Comma Separated Variable (csv) file, and any text editor or spreadsheet program that supports csv format can be used for this purpose. FieldServer Technologies provides an example configuration file so that the configuration does not need to be written from scratch.
Insert the supplied Utilities CD into the CD drive of the PC to be used for configuration and follow the install instructions. 3.5. Load the SlotServer Configuration into the SlotServer Refer to the FieldServer Utilities manual for information on the FieldServer Remote User Interface. 3.6. Program the ControlLogix CPU to communicate with the SlotServer.
The Sys indicator will indicate green if the external nodes are all communicating properly; and red otherwise. Service Pin To be used for commissioning the SlotServer into a LonWorks network FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Page 8
Rx (Receive) light will flash red if the FieldServer is receiving data. The Tx (Transmit) RS-485 light will flash red if the FieldServer is sending data. (Note that due to the nature of 2- (R1) wire RS-485 the Rx light will flash every time the Tx light flashes too). The frequency of the flashing is directly related to the frequency of data transfer.
The diagram in section 4.1 shows the ports available on the SlotServer for each of the protocols. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
The SlotServer Data Images (Data Arrays) share data with the ControlLogix CPU tags using the backplane for communication and the FieldServer Logix driver. To map the Logix Driver, the Driver needs to be configured in the SlotServer Configuration. The information that follows details the configuration parameters that can be used for this driver.
For 25 blocks we have an update rate of 25*RPI = 25*0.1 = 2.5 seconds. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Controller resides. Your Controller may be of a different type to the one shown in the example. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Click Next and choose a RPI of 100 ms. This is the rate at which the I/O image data will be transferred FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Input Data Arrays. Use the Input Image Data as Source. create Destination Tag by right clicking on Destination and choosing New Tag. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Page 18
Tag to a new Controller Tag, called Lon_In_01. Also create the Tag by right clicking on Destination and choosing New Tag. The New Tag must be of type REAL and a dimension of FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Page 19
It is very important to first make a synchronous copy of the input image data before using it. If this is not done, the input data cannot be guaranteed to be from a specific SlotServer Data Array. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Step 6: Set up the third party connection In this example, this step would involve binding the LonWorks variables using a LonWorks Network Manager.. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
1 and 2. Add more rungs with more Lon_Out_xx tags to transfer data to other output Function Blocks. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Page 22
Synchronous File Copy element. It is not permissible to update the block number into the Output Image Tag and then the data as this will cause an asynchronous transfer of data. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Image Tag and send it to the SlotServer. The SlotServer then demultiplexes the data by placing it into the appropriate Out_x Data Array depending on the block number specified in the IO image header. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Page 24
All manuals and user guides at all-guides.com...
Data_Array_Function SlotServerNodes, Bit, 256, Node_Status Note: The Data Array Name must be as shown for this function to work correctly. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
0.2s * 25 = 5s when using the full LonWorks Open Interface configuration. a message block pair consists of an output and input block FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Save the RSLogix configuration, and download it to the PLC. • The finished I/O configuration should look similar to this: FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Go Online with RSNetWorx, and then press “save”. This will transfer the RSNetWorx • Configuration to the Keeper. The final RSNetworx Configuration should look similar to this: FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
1. If offset 2 is zero, then the SlotServer is not being seen by the CPU, and Diagnostics will need to be performed using RSNetWorx and RSLogix to determine the cause of the problem. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Only one remote I/O rack is supported. • I/O can only be added online using a direct connection. • The following Vendor information provides clarification: FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Appendix A.6. Rules for Naming Logix driver Data Arrays Unlike most other FieldServer drivers, the Logix driver attaches significance to the name of the Data Array used in the Logix Driver Map Descriptor. This is done to allow the user to easily declare a series of Data Arrays to be multiplexed through the input and output buffers of the SlotServer.
Page 32
All manuals and user guides at all-guides.com...
Verify that the correct program is loaded to the CPU • Verify that the correct data types for the tags have been used. • FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...
Page 34
All manuals and user guides at all-guides.com FS-RA-CLX_SlotServer_Instruction_Manual_(T17011) Page 34 of 34 THIS PAGE INTENTIONALLY LEFT BLANK FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com...