Wrap the insulation(drain hose)around the drain hose
connection. (Fig. 10)
Fig. 10
Drain pan
Drain hose
Be sure to arrange the drain hose so that it is leveled
lower than the drain hose connecting port of the
indoor unit.
Fig. 11
OK
Arrange the drain hose
lower than this portion
Do not install the unit so that the drain
hose side is too high. Height A should
be less than 5 mm. (Fig. 12)
Fig. 12
Drain hose
A
BAD
B. UNDER CEILING TYPE
Using the installation template, drill holes for piping
and anchor bolts(for holes). (Fig. 13)
Fig.13
35.4" (900 mm)
Installation
7-7/8"
template
(200 mm)
Drilling position
for piping
Insulation
(Drain hose)
NO
NO
Drain hose
A
BAD
Drilling position
for anchor bolt
Ceiling
Wall
1. DRILLING FOR PIPING
Select piping and drain directions. (Fig.14)
Fig. 14
Install the drain hose at the rear; it
should not be installed on the top or
right side.
When the directions are selected, drill 3-1/8" (80 mm)
and 2"(50 mm) or 6"(150 mm) dia. hole on the wall so
that the hole is tilted downward toward the outdoor
for smooth water flow.
Fig. 15
Wall
Indoor side
2. DRILLING HOLES FOR ANCHOR BOLTS AND
INSTALLING THE ANCHOR BOLTS.
With a concrete drill, drill four 1/2 "(12.7 mm)dia
holes. (Fig. 16)
Fig. 16
Insert the anchor bolts into the drilled holes, and drive
the pins completely into the anchor bolts with a ham-
mer. (Fig. 17)
Fig. 17
6
Top
Rear
(Install the drain hose
in this direction.)
Right
1/4" (6 mm)
Outdoor side
2-3/8" to 2-3/4"
(60 to 70 mm)
ø1/2" (12.7 mm)