GE 40350 Installation And Start-Up Manual page 15

Home generator system
Hide thumbs Also See for 40350:
Table of Contents

Advertisement

Available languages

Available languages

Generator installations
NOTICE The figures below show the minimum installation distances allowed to structures and items listed in legend.
A
Exhaust
Direction
B
5 ft (1.5 m)
Structure
18 in (45.7 cm) min
Standby
A
Standby weatherproof enclosure must be at least 5 ft
A
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Exhaust outlet side of weatherproof enclosure must
B
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby weatherproof enclosure must have a
C
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
Structure
5 ft (1.5 m) min
Standby
A
Exhaust
Direction
B
5 ft
(1.5 m)
A
A
Structure
18 in (45.7 cm) min
Standby
5 ft
(1.5 m)
Exhaust
Direction
B
Structure
18 in (45.7 cm) min
5 ft (1.5 m) min
Standby
5 ft (1.5 m)
Exhaust
Direction
B
A
5 ft (1.5 m) min
A
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

40374

Table of Contents