Check Points - Vivax ACP-18CH50GEEI Service Manual

Table of Contents

Advertisement

Malfunction indicator of outdoor unit

check points:

Out of step occurs once
the unit is powered on
N
Is stop time of the
compressor longer than
3 minutes?
Are the wires for the
compressor connected correctly? Is the
connection made in clockwise
direction?
N
Connect the
wires correctly
Replace the control
panel AP1
Y
If the fault is eliminated?
Replace the
compressor
Fault with
Y
Is heat dissipation of the unit
Is the input voltage normal?
Y
N
End
Out of step occurs in
operation
Is the outdoor fan working
N
normally?
Y
Y
N
N
abnormal?
Y
Is the
Y
charge volume of refrigerant
too much?
N
Replace the control
panel AP1
If the fault is eliminated?
Y
N
Replace the
compressor
End
Check if the fan terminal
Replace the fan
OFAN is connected correctly
capacitor C1
Replace the
Improve the heat dissipation
outdoor fan
of the unit(eg. clean heat
exchanger, improve
ventilation, etc.)
Start the unit after input
volatge is normal
Charge refrigerant according
to the service manual