Recommended Venting Practice; Leak Test (For Coaxial Venting Systems Only) - Viessmann Vitodens 100-W WB1B Series Installation Instructions Manual

Rigid pipe venting systems
Table of Contents

Advertisement

General Information
General Installation Information

Recommended venting practice

Leak test (for coaxial venting systems only)

Viessmann recommends that the heating contractor perform
a simplified leak test during boiler start-up. For this purpose
it is sufficient to measure the CO
combustion air in the annular gap of the air intake pipe.
The vent pipe is considered sufficiently leak-proof if a CO
concentration in the combustion air no higher than 0.2%
or an O
concentration no lower than 20.6% is measured
2
relative to a starting O
2
12
concentration of the
2
concentration of 20.9%.
Rigid Venting Systems Installation Instructions
(continued)
When installing a venting system the following
recommended venting practices apply:
Keep length and number of 90º elbows to a minimum.
g
Try not to use back-to-back 90º elbows.
g
Use 45º elbows where possible to minimize the number
g
of 90º elbows in case redirection of flue gas is required.
The special vent system shall not be routed into,
g
through, or within any other vent such as an existing
masonry or factory-built chimney.
Exception:
A masonry chimney flue may be used to route the venting
system only if no other appliance is vented in the same flue.
If higher CO
values or lower O
2
inspect the venting system thoroughly.
Continuous short cycling of the boiler can indicate a leaking
venting system.
2
Note: The vent pipe adaptor comes with two measurement
ports, one for combustion air intake measurement
and one for flue gas measurement.
values are measured,
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 200-w wb2b series

Table of Contents