Data Format - Smart temp SMT - 131 Manual

Hide thumbs Also See for SMT - 131:
Table of Contents

Advertisement

Data Format

Protocol
Byte Format
Address
Baud
Holding
Type
Register
40001
Read Only
40002
Read Only
40003
Read Only
40004
Read / Write
40005
Read Only
40006
Read / Write
40007
Read / Write
40008
Read / Write
Modbus RTU
1 Start Bit, 8 Data Bits, 1 Stop Bit, No Parity
1 to 255
4800 / 9600 / 19200 BPS
Value
Device ID
Firmware Version
DIP Switch
Settings
Occupancy Status
Bell Status
Door Station
Status
HVAC Status
Fan Status
Page 12
Comments
Always Returns "131"
Use As A Sentinel Point
Divide By 100 (e.g. Version 2.36 = 236)
Binary Count
Sw 1 = 1, Sw2 = 2, Sw3 = 4, Sw 4 = 8 etc
0 = Room is Unoccupied
1 = Room is Occupied
Note - Modbus can write "0" holding the
room unoccupied regardless of the occupancy
input.
Modbus cannot override the occupancy input
and hold the SMT-131 in occupied mode.
0 = Bell Is Silent
1 = Bell Is Chiming
0 = Normal - No Activity
1 = "Make Up Room" Active
2 = "Do Not Disturb" Active
0 = Air Conditioning Off (1 or 3 Fan Speed)
1 = Low Speed Ventilation ( 1 or 3 Fan Speed)
2 = Med Speed Ventilation (3 Fan Speed Only)
3 = High Speed Ventilation (3 Fan Speed only)
4 = Air Conditioning ON (1 or 3 Fan Speed)
3 Fan Speed Mode
0 = Low (Fan Auto)
1 = Med ( Fan Auto)
2= High (Fan Auto)
3 = Auto Fan Speed (Fan Auto)
4 = Low (Fan On)
5 = Med (Fan On)
6 = High (Fan On)
7 = Auto Fan Speed (Fan On)
1 Fan Speed Mode
0 = Fan Auto
4 = Fan On