Vanguard BHDV34N(A) Owner's Operation And Installation Manual page 20

Direct-vent fireplace
Hide thumbs Also See for BHDV34N(A):
Table of Contents

Advertisement

DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
FIREPLACE
INSTALLATION
Continued
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1.
Close manual shutoff valve (see Fig-
ure 37).
2.
Pressurize supply piping system by ei-
ther opening propane supply tank valve
for propane gas fireplace or opening
main gas valve located on or near gas
meter for natural gas fireplace, or using
compressed air.
3.
Check all joints from propane supply
tank or gas meter to manual shutoff
valve (see Figure 38 for propane or Fig-
ure 39 for natural). Apply commercial
leak test solution to all gas joints.
Bubbles forming show a leak. Correct
all leaks at once.
Pressure Testing Fireplace Gas
Connections
1.
Open manual shutoff valve (see Figure
37).
2.
Open propane supply tank valve for
propane fireplace or main gas valve lo-
cated on or near gas meter for natural
gas fireplace.
3.
Make sure control knob of fireplace is
in the OFF position.
4. Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 38 for propane or Figure 39 for natu-
ral). Apply commercial leak test solu-
tion to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.
5.
Light fireplace (see Operating Fire-
place, pages 25 throught 27). Check all
other internal joints for leaks.
6. Turn off fireplace (see To Turn Off Gas
to Appliance, page 25).
®
Manual
Shutoff
Valve
Figure 37 - Manual Shutoff Valve
Propane Supply Tank
Manual
Shutoff Valve
Figure 38 - Checking Gas Joints for Propane/LP Gas Fireplace
Manual
Shutoff Valve
Gas Meter
Figure 39 - Checking Gas Joints for Natural Gas Fireplace
20
Open
ON
POSITION
OFF
Closed
POSITION
Gas Valve
Gas Valve
105454