Saunier Duval 47-920-36 Instructions For Use Installation And Servicing page 34

Fanned flue combination boiler
Table of Contents

Advertisement

• Drain the boiler, refer to diagram 17.2.
• On completion check all gas-carrying parts for soundness with
leak detection fluid.
17.3 Front panel
• Unscrew and remove the two retaining screws from the bottom
of the front panel.
• Remove front panel by lifting up and forward.
17.4 Control panel
• Lower forwards to gain access to lower part of boiler.
17.5 Sealed chamber cover
• Unscrew and remove the two retaining screws from the sealed
chamber cover, see diagram. 17.3.
• Lift cover up and off pins on top of boiler.
17.6 Side panels (for ease of access if
available), refer to diagram 17.4
• Unscrew and remove the two retaining screws from front of
each side panel.
• Left hand side panel only disconnect the control panel
retaining strap at the control panel.
• Unhook each panel from the front retaining tabs.
• Pull each panel forward from the rear retaining tabs to
remove.
4000123924-2
17 Routine Cleaning and Inspection
34
Diagram 17.3
F30E shown
Diagram 17.4