Outlines And Dimensions - Mitsubishi Electric Mr.SLIM PUHZ-RP35VHA2 Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.SLIM PUHZ-RP35VHA2:
Table of Contents

Advertisement

7

OUTLINES AND DIMENSIONS

PUHZ-RP35/50VHA2
PUHZ-RP35/50VHA3
Air intake
33 drain hole
45.4
4-10 21 oval hole
(M10 foundation bolt)
18
Handle for
moving
150
287.5
Free space around the outdoor unit
(basic example)
100 mm or more as long as
no obstacle is placed on the
rear and right-and-left sides
of the unit.
1
2
2 sides should be open in
the right, left and rear side.
Minimum installation space for outdoor unit
1 In the place where short cycle tends to occur, cooling and heating
capacity and power consumption might get lowered 10%. Air outlet
guide (optional PAC-SG58SG) will help them improve.
2 If air discharges to the wall, the surface might get stained.
(1)
400
33 drain hole
347.5
Air intake
Air discharge
Installation bolt pitch: 500
800
1
23
40
69
Service port
1. FOUNDATION BOLTS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts, washer and nut must
be purchased locally.)
<Foundation bolt height>
FOUNDATION
Conduit hole
20
Service panel
Service panel
for charge plug
Connection for
liquid pipe
Connection for
gas pipe
183
2. PIPING-WIRING DIRECTION
Piping and wiring connection can
be made from the rear direction only.
3. ATTACHING THE CONDUIT
In order to attach the conduit, it is
necessary to fix the metal plate with
2 screws to the back panel. Procure
the metal plate and make screw holes
locally. It is recommended to use the
metal plate shown below. Align the
metal plate to the marks on the unit
and attach it.
The position and the size of
conduit hole depend on the
conduit to be used.
Holes for metal plate fixing screw
The size of hole depends on the
screw to be used.
Unit : mm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents