Download Print this page

Vivax ACP-24COFM70GEI Service Manual page 20

Hide thumbs Also See for ACP-24COFM70GEI:

Advertisement

9.Disassemble valve support sub-assy, bidirectional liquid
liquid storage tank (valve support sub-assy should include
gas, liquid valves, valve support, air collective pipe,
electric magnetic expansion valve, diffluence pipe)
Unscrew the bolts which fixed the valve support, unsolder the soldered points
on bidirectional liquid storage tank, take off the valve support sub-assy (the
air collective pipe is connected with 4-way valve).
10.Disassemble Compressor
Open the soundproofing cotton, Unsolder the pipe-
line connecting the compressor, and then unscrew
the 3 foot-nuts fixing conpressor to remove it.
Valve support
Air collective pipe
Electric magnetic expansion valve
Diffluence pipe
G a s - L i q u i d
Separator
S o u n d p r o o f i n g
Cotton
Silencer
Compressor
18
Bidirectional liquid storage tank
Weld
Soldered points
Nut

Advertisement

loading

This manual is also suitable for:

Acp-28cofm80gei