SW2 setting
The number of connected indoor units
ON
1
2 3 4 5 6
Capacity setting display
ON
1
2 3 4 5 6
Outdoor unit setting information
ON
1
2 3 4 5 6
Indoor pipe temperature / Liquid (TH2(1))
Indoor 1
ON
– 39~88
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
(TH5(1))
ON
Indoor 1
– 39~88
1
2 3 4 5 6
Indoor pipe temperature / Liquid (TH2(2))
Indoor 2
ON
– 39~88
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
(TH5(2))
ON
Indoor 2
– 39~88
1
2 3 4 5 6
Indoor room temperature (TH1)
8~39
ON
1
2 3 4 5 6
OCH527
Display detail
87
The black square ( ) indicates a switch position.
Explanation for display
0~4
(The number of connected indoor units are dis-
played.)
Displayed as an outdoor capacity code.
Capacity
Code
ZRP35V
9
ZRP100V, 100Y
ZRP50V
10
ZRP125V, 125Y
ZRP60V
11
ZRP140V, 140Y
ZRP71V
14
• The tens digit (Total display for applied setting)
Setting details
Display details
H·P / Cooling only
0 : H·P
Single phase / 3 phase
0 : Single phase 2 : 3 phase
• The ones digit
Setting details
Display details
Defrosting switch
0 : Normal
(Example) When heat pump, 3 phase and defrosting
(normal) are set up, "20" is displayed.
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
8~39
Capacity
Code
20
25
28
1 : Cooling only
1 : For high humidity
Unit
Unit
Code
display
Code
display
:
:
:
:
: