13-2-2. PAR-21MAA

Remote controller button position

Compressor information Outdoor unit information Indoor unit information
Operation mode
[Display
]
Refrigerant leakage
detection
(initial teaching)
GAS LEAK
TEST START
] Waiting for stabilization
[Display
OCH527
This air conditioner (Outdoor unit) can detect refrigerant leakage
which may happen during a long period of use. In order to enable
the leakage detection, the following settings are required to let the
unit memorize the initial condition (initial refregerant amount).
Make sure to perform the "test run" and confirm the unit works
Confirm
without any problems, before starting the following setting.
For more precise detection, make sure to set the airflow at
"High notch" before enabling this setting.
1.How to select the "Refrigerant Leakage Detection" mode
Refrigerant leakage
Detection is possible regardless the unit`s operation (ON or OFF).
detection judgement
Press
"EASY MAINTENANCE" mode.[Display
GAS LEAK
JUDGE
2.How to start the initial learning
Press
* The initial learning for the leakage detection is always done once after
the new installation or the data reset.
After 45 minutes
Press
How to finish the initial learning
Once the unit`s operation is stabilized, the initial learning is completed.
Press
The initial learning can also be cancelled by pressing
Caution :
button for more than 3 seconds to switch to
TEST
CLOCK
button and select the [GAS LEAK TEST START]
Stabilized
( )button to confirm.
FILTER
button for more than 3 seconds to cancel the initial leaning.
TEST
122
]
button.
ON/OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents