Function Of Connector; Special Function; Low-Level Sound Priority Mode (Local Wiring); On Demand Control (Local Wiring) - Mitsubishi Electric Mr.Slim PUHZ-ZRP35VKA Service Manual

Split-type, heat pump air conditioners r410a
Hide thumbs Also See for Mr.Slim PUHZ-ZRP35VKA:
Table of Contents

Advertisement

(2) Function of connector

Types
Connector
Connector
CN31

Special function

(a) Low-level sound priority mode (Local wiring)
By performing the following modifi cation, operation noise of the outdoor unit can be reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to
the CNDM connector (option) on the control board of the outdoor unit.
• The ability varies according to the outdoor temperature and conditions, etc.
1 Complete the circuit as shown when using the external input adapter (PAC-SC36NA-E). (Option)
2 SW7-1 (Outdoor unit control board): OFF
3 SW1 ON: Low noise mode
SW1 OFF: Normal operation
A
X
SW1
(b) On demand control (Local wiring)
By performing the following modifi cation, energy consumption can be reduced to 0–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to
the CNDM connector (option) on the control board of the outdoor unit.
1 Complete the circuit as shown when using the external input adapter (PAC-SC36NA-E). (Option)
2 By setting SW7-1 on the control board of the outdoor unit, the energy consumption (compared to the normal consumption) can
be limited as shown below.
SW7-1
SW2
OFF
ON
Demand
ON
function
ON
OFF
A
X
Y
X
SW2
SW3
Y
OCH527
Function
Emergency operation
C
D
CNDM
Orange
X
Brown
Red
SW3
Energy consumption
OFF
100%
OFF
75%
ON
50%
ON
0% (Stop)
C
D
CNDM
Orange
Brown
Red
Action by open/ short operation
Short
Start
A Circuit diagram example
(low noise mode)
1
B On-site arrangement
3
C External input adapter
(PAC-SC36NA-E)
A Circuit diagram example
1
(Demand function)
B On-site arrangement
3
X, Y: Relay
81
Effective timing
Open
When power supply ON
Normal
X: Relay
D Outdoor unit control board
E Max. 10 m
F Power supply for relay
C External input adapter
(PAC-SC36NA-E)
D Outdoor unit control board
E Max. 10 m
F Power supply for relay