DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is avail-
able for connecting side ducts.
For bottom duct applications:
1. Remove the side panels from the supply and return
air compartments to gain access to the bottom
supply and return air duct covers.
2. Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.)
3. Replace the side supply and return air compartment
panels.
For side duct applications;
1. Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2. Connect ductwork to the duct flanges on the rear of
the unit.
DETAIL "X"
(ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS)
FIG. 10 - DIMENSIONS & CLEARANCES - 15 & 20 TON
Unitary Products Group
RETURN AIR
SUPPLY AIR
CONDENSER AIR
OUTDOOR AIR
(Economizer)
All dimensions are in inches. They are sub-
ject to change without notice. Certified di-
mensions will be provided upon request.
UTILITIES ENTRY DATA
OPENING
HOLE
SIZE
(DIA.)
1-1/8" KO
A
3/4" NPS (Fem.)
3-5/8" KO
B
3" NPS (Fem.)
C
2-3/8" KO
D
1-11/16" Hole
*Opening in the bottom of the unit can be located by the slice
in the insulation.
CLEARANCES
Front
36"
24" (Less Economizer)
Back
49" (With Economizer)
24" (Less Economizer)
Left Side (Filter Access)
36"
Right Side (Cond. Coil)
36"
1
Below Unit
20"
72" With 36" Maximum
2
Above Unit
1Units (applicable in U.S.A. only) may be installed on combustible floors
made from wood or class A, B or C roof covering material.
2
Units must be installed oudoors. Overhanging structures or shrubs should
not obstruct condenser air discharge outlet.
3
If economizer is factory installed, the assembled hood kit must be removed
prior to final installation. This hood is 54" long.
NOTE:
A one-inch clearance must be provided between any combustible material
and the supply air ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to accumulate within a
confined space and recirculate.
Locate unit so that the vent air outlet hoods are at least:
Three (3) feet above any forced air inlet located within 10 horizontal feet
(excluding those integral to the unit).
Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity
air inlet into the building.
Four (4) feet from electric meters, gas meters, regulators and relief equip-
530.18-N6Y
USED FOR
Front
Control
Wiring
Bottom
Front
Power
Wiring
Bottom
Gas Piping (Front)
Gas Piping (Bottom)*
3
(With Economizer)
Horizontal Overhang
(For Condenser Air
Discharge Outlet)
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D2cg180D2cg240

Table of Contents