Set Temperature Rise - Carrier 58TUA Installation, Start-Up, And Operating Instructions Manual

2-speed, 2-stage induced-combustion gas furnace
Table of Contents

Advertisement

Table 9—Gas Rate (Cu Ft/Hr)
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
100
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
adjust the manifold pressure (see item c) and replace the main
burner orifices as needed. Refer to NFGC Appendix F, Table F-4
for proper orifice sizing at high altitudes.
NOTE: Canadian installations only—The Canadian ratings are
approved for altitudes up to 2000 ft for natural and propane gases.
High-altitude ratings are from 2000 ft to 4500 ft above sea level.
High-altitude rating includes a 10 percent derate as required by
Canadian standards.
(9.) Measured gas inputs should equal low- and high-fire
gas inputs on unit rating plate ± 2 percent.
(10.) Proceed to item c. to adjust manifold pressure.
DO NOT redrill burner orifices. Improper drilling (burrs, out-
of- round, etc.) can cause excessive burner operating noise
and misdirection of burner flames. This could result in flame
impingement on burners and heat exchanger surfaces, leading
to potential failures.
c. Adjust gas manifold pressure
(1.) Move SW-2 to the ON position to lock out the
adaptive algorithm. (See Fig. 10 and 11.) Jumper R to
W/W1 and W2 to call for high-gas heat.
(2.) Remove gas control regulator adjustment seal caps.
(See Fig. 13.)
(3.) Turn high-fire adjusting screw (5/64-in. hex Allen
wrench) counterclockwise (out) to decrease input rate
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
50
72
144
360
51
71
141
355
52
69
138
346
53
68
136
340
54
67
133
333
55
65
131
327
56
64
129
321
57
63
126
316
58
62
124
310
59
61
122
305
60
60
120
300
62
58
116
290
64
56
112
281
66
54
109
273
68
53
106
265
70
51
103
257
72
50
100
250
74
48
97
243
76
47
95
237
78
46
92
231
80
45
90
225
82
44
88
220
84
43
86
214
86
42
84
209
88
41
82
205
90
40
80
200
92
39
78
196
94
38
76
192
96
38
75
188
98
37
74
184
100
36
72
180
102
35
71
178
104
35
69
173
106
34
68
170
108
33
67
167
110
33
65
164
112
32
64
161
116
31
62
155
120
30
60
150
or clockwise (in) to increase rate. When adjusting
input rate, DO NOT set manifold pressure less than
3.2-in. wc or more than 3.8-in. wc for natural gas. If
manifold pressure is outside this range, change main
burner orifices.
(4.) Remove R-to-W2 jumper to place furnace in low-fire
operation for low-fire adjustment.
(5.) Turn low-fire adjusting screw (5/64-in. hex Allen
wrench) counterclockwise (out) to decrease input rate
or clockwise (in) to increase rate. When adjusting
input rate, DO NOT set manifold pressure less than
1.3-in wc or more than 1.7-in. wc for natural gas. If
manifold pressure is outside this range, change main
burner orifices.
NOTE: If orifices are changed, both high-fire and low-fire input
rates must be readjusted, with manifold pressures within ranges
specified in items (3.) and (5.).
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check the orifice size with a numbered drill bit of
the correct size. Never use a redrilled orifice. A burr-free and
squarely aligned orifice hole is essential for proper flame charac-
teristics.
(6.) Remove jumper on R-W/W1 after low-fire adjust-
ments.
(7.) When correct input is obtained, replace regulator seal
caps. Main burner flame should be clear blue, almost
transparent. (See Fig. 14.)

2. Set temperature rise.

Place SW-2 in ON position. Jumper R to W/W1 and W2 to
check high-gas-heat temperature rise. To check low-gas-heat
temperature rise, remove jumper to W2. Determine air tem-
perature rise for both high and low fire. Do not exceed the
temperature rise ranges specified on the unit rating plate for
high and low fire.
a. Place duct thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not see heat
exchangers so that radiant heat will not affect thermometer
readings. This is particularly important with straight run
ducts.
MANUAL
ON/OFF
INLET
PRESSURE
TAP
MANIFOLD
PRESSURE
TAP
Fig. 13—Redundant Automatic Gas Control Valve
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine tem-
perature rise.
NOTE: If the temperature rise is outside this range, first check:
15
LOW-FIRE
ADJUSTMENT
ALLEN SCREW
(UNDER CAP)
HIGH-FIRE
ADJUSTMENT
ALLEN SCREW
(UNDER CAP)
A93376

Advertisement

Table of Contents
loading

Table of Contents