Sound Ratings - York AM012M1021 Technical Manual

Split-system air conditioners 10 seer (1 thru 2.5 nominal tons, 1 ph)
Table of Contents

Advertisement

036-21573-001 Rev. A (0304)
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
MODEL
AM012M1021
N1AHB0806
AM018M1021
N1AHB0806
AM024M1021
N1AHB0806
AM030M1021
N1AHB1206
AM012M1021
F2RP018
AM018M1021
F2RP/F2FP018
AM018M1021
F2RP/F2FP024
AM024M1021
F2RP/F2FP024
AM030M1021
F2RP/F2FP030
AM030M1021
F2RP/F2FP036
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240.
Cooling MBH based on 95°F outdoor ambient, 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU's divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in
watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP
5. F2RP air handlers have B.O.D (Blower on Delay) standard.
- = Not applicable.
ACCESSORIES*
Refer to Price Manual for specific model numbers.
Hard Start Kit - Provides increased starting torque for areas
with low voltage.
Compressor Blanket - Designed to further reduce the nor-
mal compressor operating sound. Refer to price pages for
specific match-ups.
Off Cycle Timer Delay - Provides a 5-minute off cycle to pre-
vent rapid recycling of the compressor.
Room Thermostats - A wide selection of compatible thermo-
sets are available to provide optimum performance and fea-
tures for any installation.
1 Heat Stage only, manual, mechanical thermostat. Add sub-
base for 1H/1C.
1H/1C, manual change-over electronic non-programmable
thermostat.
4
AIR HANDLER
2
ELECTRIC
W
HEAT KW
1 PH 10 SEER AC WITH N1AH / G2FD
10
17
10
17
10
17
10,15,18
17
1 PH 10 SEER AC / F2RP
2,5,8
18
2,5,8
18
5,8,10
18
5,8,10
18
5,8,10,15
18
5,8,10,15,19
21
.
All ratings remain the same.
1
COIL
RATED
MODEL
CFM
TOTAL SENS.
G2FD024(S,H)17
450
G2FD024(S,H)17
650
G2FD024(S,H)17
850
G2FD030(S,H)17
1050
4
5
,
-
500
-
650
-
650
-
850
-
1050
-
1050
1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the
price book or consult factory.

SOUND RATINGS*

UNIT MODEL
012
018
024
030
*Rated in accordance with ARI Standard 270.
COOLING
NET MBH
SEER
SEER
W/O TXV
+ TXV
14.5
10.4
10.00
18.6
13.4
10.00
23.4
16.8
10.00
28.2
20.3
10.00
14.5
10.6
10.00
17.4
12.6
10.00
18.6
13.4
10.00
23.4
16.8
10.00
28.4
20.3
10.00
29.0
20.7
10.00
SOUND
RATINGS
DBA
72
74
75
76
Unitary Products Group
EER
3
-
10.00
-
9.50
-
9.15
-
9.00
-
9.70
-
9.35
-
9.50
-
9.15
-
9.05
-
9.15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Am024m1021Am018m1021Am030m1021

Table of Contents