After the initial 8-hour minimum warmup, continue with start-
up:
2
Press the Next arrow on the control to move
to the Main screen.
The Main screen displays:
STATUS
SETUP RUN ALM
3
Press the Run arrow.
STATUS
SETUP RUN ALM
The Run screen displays:
RUN
4
Press the RUN arrow.
Verify that the Chiller begins to run. Check that the
Compress light and the Process Pump light on the control
panel are lit.
5
Check the rotation of the pump.
If pump is not turning, disconnect main power to chiller,
swap any two wires; reapply main power. Check for
leaks.
6
If you get an alarm message on the display:
If you get a Compressor Backwards, Shut Off, Swap
Leads message, press the Stop Chiller button, unplug
Chiller from main power supply, switch any two compres-
sor leads, and apply main power supply. Wait three min-
utes and then press Run arrow.
7
Press the Escape/Previous button to
return to the Main screen.
UGH017/0500
press arrow
PUMPDOWN
press arrow
Series 1 Portable Chillers, PLC Control
I
NITIALLY
S
TARTING THE
C
HILLER
'
CONT
D
When the compressor is shut
off it cannot be turned on
again for three minutes. This
allows temperatures and
pressure in the chiller to
equalize, making restart easi-
er, and prolonging the life of
the chiller.