Connecting the wiring: EKEXDCBAV3
Connect the wires to the terminal board according to the wiring
diagram in
figure
5. See
box. The wiring intake hole indication H1 refers to the H1 cable
of the corresponding wiring diagram.
Connect cables according to specifications of the next table.
Table connection and application
Description
L, N,
Power supply
earth
Expansion valve
Y1~Y6
connection
Thermistor R2T
R1,R2
(liquid pipe)
Thermistor R3T
R3,R4
(gas pipe)
R5,R6
Thermistor R1T (air)
P1,P2
Remote controller
Communication to
F1,F2
outdoor unit
T1,T2
ON/OFF
Capacity step
Error signal
Operation signal
(*) Recommended size (all wiring must comply with local codes).
Wiring diagram
A1P.................... Printed circuit board
F1U.................... Fuse (250 V, F5A)(A1P)
F3U.................... Field fuse
HAP ................... Light emitting diode (service monitor-green)
KRP4 ................. Optional connection PCB
Q1DI .................. Earth leakage breaker
R1T.................... Thermistor (air)
R2T.................... Thermistor (liquid)
R3T.................... Thermistor (gas)
T1R.................... Transformer (220 V/21.8 V)
X1M,X3M........... Terminal block
Y1E.................... Electronic expansion valve
X1M-R1/R2........ Thermistor liquid
X1M-R3/R4........ Thermistor gas
X1M-R5/R6........ Thermistor air
X1M-Y1~6 ......... Expansion valve
X1M-P1/P2 ........ Communication remote controller
X1M-T1/T2......... Input: ON/OFF
X1M-F1/F2......... Communication outdoor unit
........... Field wiring
L......................... Live
N ........................ Neutral
,
......... Connector
........................ Wire clamp
..................... Protective earth (screw)
............... Separate component
............... Optional accessory
BLK.................... Black
BLU.................... Blue
EKEXFCBAV3 + EKEXDCBAV3
Option kit for combination of Daikin condensing units
with field supplied evaporators
4PW30903-1
figure 6
for wiring intake in the control
Connect to
Type of cable
Power supply
H05VV-F3G2.5
Expansion valve kit
LIYCY3 x 2 x 0.75
H05VV-F2 x 0.75
Outdoor unit
Controller field supply
LIYCY4 x 2 x 0.75
Cross section
Maximum length
2
(*)
(mm
)
(m)
2.5
20
Standard: 2.5
Max.: 20
0.75
100
Optional connection: when the function of the switch box needs to be
extended: see KRP4A51 for details of settings and instructions.
BRN ................... Brown
GRN ................... Green
GRY ................... Gray
ORG................... Orange
PNK.................... Pink
RED ................... Red
WHT................... White
YLW ................... Yellow
Specifications
Power supply 230 V 1~50 Hz
Digital output 12 V DC
Analog input 16 V DC
Communication line 16 V DC
Digital input 16 V DC
Installation and operation manual