NSTALLATION OF THERMISTORS
Refrigerant thermistors
Location of the thermistor
A correct installation of the thermistors is required to ensure a good
operation:
1.
Liquid (R2T)
Install the thermistor behind the distributor on the coldest pass
of the heat exchanger (contact your heat exchanger dealer).
2.
Gas (R3T)
Install the thermistor at the outlet of the heat exchanger as close
as possible to the heat exchanger.
Evaluation must be done to check if the evaporator is protected
against freeze-up.
Execute test operation and check for freeze-up.
1
Liquid R2T
2
Gas R3T
Installation of the thermistor cable
1
Put the thermistor cable in a separate protective tube.
2
Always add a pull-relief to the thermistor cable to avoid strain on
the thermistor cable and loosening of the thermistor. Strain on
the thermistor cable or loosening of the thermistor may result in
bad contact and incorrect temperature measurement.
Installation and operation manual
7
1
1
2
4 5
°
Fixation of the thermistor
Put the thermistor wire slightly down to avoid water
accumulation on top of the thermistor.
Make
evaporator. Put the top of the thermistors on the
evaporator, this is the most sensitive point of the
thermistor.
1
Most sensitive point of the thermistor
2
Maximize the contact
1
Fix the thermistor with insulating aluminum tape (field supply) in
order to ensure a good heat transference.
2
Put the supplied piece of rubber around the thermistor
2
(R2T/R3T) in order to avoid loosening of the thermistor after
some years.
3
Fasten the thermistor with 2 tie wraps.
4
Insulate the thermistor with the supplied insulation sheet.
Air thermistor (only for EKEXDCB)
The air thermistor (R1T) can be installed either in the room that
needs temperature control or in the suction area of the evaporator.
NOTE
For room temperature control the delivered thermistor
(R1T) can be replaced by an optional remote sensor
kit KRCS01-1(A) (to be ordered separately).
good
contact
between
thermistor
1
2
4 5
°
EKEXFCBAV3 + EKEXDCBAV3
Option kit for combination of Daikin condensing units
with field supplied evaporators
and
4PW30903-1

Advertisement