Pioneer WAE012AMFI15RL Service Manual page 37

Wae-wye series single split dc inverter air conditioner / heat pump systems
Table of Contents

Advertisement

8.4.6.2 In forced operation mode, all general
protections and remote control is available.
8.4.6.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and
indoor fan runs as breeze speed. After running
for 30 minutes. the machine will turn to auto
mode with 24℃ setting temperature.
Forced auto mode:
The action of forced auto mode is the same as
normal auto mode with 24℃ setting
temperature.
8.4.7 Timer function
8.4.7.1 Timing adjustable range is 24 hours.
8.4.7.2 Timer on. The system will turn on
automatically when reaching the set time.
8.4.7.3 Timer off. The system will turn off
automatically when reaching the set time.
8.4.7.4 Timer on/off. The system will turn on
automatically when reaching the set "on" time,
and then turn off automatically when reaching
the set "off" time.
8.4.7.5 Timer off/on. The system will turn off
automatically when reaching the set "off" time,
and then turn on automatically when reaching
the set "on" time.
8.4.7.6 The timer function will not change the
unit's current operation mode. If the unit is off
now, it will not start after setting the "timer off"
function. And when reaching the setting time,
the timer LED will be off and the running mode
will not be changed.
8.4.7.7 The setting time is relative time.
8.4.8 Sleep function mode
8.4.8.1 Operation time in sleep mode is 7 hours.
After 7 hours the system quits this mode and
turns off.
8.4.8.2. Operation process in sleep mode is as
follows:
When cooling, the setting temperature rises 1℃
(if room is lower than 30℃) every one hour, 2
hours later the setting temperature stops rising
and indoor fan is fixed as low speed.
When heating, the setting temperature
decreases 1℃ (if room is higher than 17℃)
every one hour, 2 hours later the setting
temperature stops rising and indoor fan is fixed
as low speed. (Warm-Start function has the
priority)
8.4.8.3 Timer setting is available
8.4.8.4 When user uses timer off function in
sleep mode (or sleep function in timer off mode),
if the timing is less than 7 hours, sleep function
will be cancelled when reaching the setting time.
If the timing is more than 7 hours, the machine
will not stop until reaching the set time in sleep
mode.
8.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart
function, which is carried out through an
auto-restart memory module. In case of a
sudden power failure, the module memorizes
the setting conditions before the power failure.
The unit will resume the previous operation
setting (not including swing function)
automatically after 3 minutes when power
returns.
If the auto restart condition occurs in forced
cooling mode, the unit will run in cooling mode
for 30 minutes and turn to auto mode at 24℃
set temp.
If system is off before power goes out it will stay
off. When the unit is started up by the user, the
compressor will have 1 minute delay. For other
conditions, the compressor will have 3 minutes
delay when restarts.
8.4.10 8℃ Heating (Vacation Mode -
Optional)
In heating operation, the preset temperature of
the air conditioner can be as lower as 8℃,
which keeps the room temperature steady at 8℃
and prevents household items from freezing
when the house is unoccupied for a long time in
severe cold weather (Vacation Mode)
35