A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING
MODEL
A36F
THREE PHASE

BATTERY CHARGER

ECN/DATE
12251 - 8/98
12444 – 11/98
10845 – 4/97
106 BRADROCK DRIVE
DES PLAINES, IL. 60018
(847) 299-1188
FAX: (847) 299-3061
ISSUE DATE: 9842 – 11/95
INSTRUCTION DRAWING NUMBER:
LA36F3PHASE-1

Advertisement

Table of Contents
loading

Summary of Contents for Lamarche A36F

  • Page 1: Battery Charger

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING MODEL A36F THREE PHASE BATTERY CHARGER ECN/DATE 12251 - 8/98 12444 – 11/98 10845 – 4/97 106 BRADROCK DRIVE DES PLAINES, IL. 60018 (847) 299-1188 FAX: (847) 299-3061 ISSUE DATE: 9842 – 11/95...
  • Page 2: Personal Precautions

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING IMPORTANT SAFETY INSTRUCTIONS FOR THE LA MARCHE POWER CONVERSION EQUIPMENT SAVE THESE INSTRUCTIONS This manual contains important safety and operating instructions for the La Marche Power Conversion Equipment. Before using this equipment, read all instructions and cautionary markings on (1) unit, (2) battery, and (3) product using the battery.
  • Page 3: Unit Location

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING Ø Ø Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery. A battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn.
  • Page 4: Receiving Instructions

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING RECEIVING INSTRUCTIONS GENERAL EQUIPMENT INFORMATION CAUTION: To ensure safe installation and operation, the information given in the instruction manual should be read and understood before installing or using the equipment. RECEIVING INSTRUCTIONS Unpacking and Inspection: Examine the shipping crate upon arrival.
  • Page 5: Output Ratings

    The solid state electronic control circuit provides excellent line-load voltage regulation, current limiting, timer, and alarm package with relays are standard. The Model A36F-3 PHASE is available in a wide range of a.c. input voltages, with 24 volt and 48 volt d.c. outputs in output currents ranging from 100 to 400 amps.
  • Page 6: Input Ratings

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING 3.0 INPUT RATINGS A.C. VOLTAGE The units are rated for three phase inputs and are available in 208/ 240 or 480 v.a.c. three phase inputs. INPUT FREQUENCY RANGE 57 to 63 Hz. (60 HZ nominal) 47 to 57 HZ.
  • Page 7: Status/Alarm Indicators

    A load sharing circuit is provided on the terminal board. When connected, two (2) or more La Marche A36F-3 PHASE units are forced to share the load equally within +/- 5%. Individual unit d.c. amp output must be greater than 10% of nameplate rated output.
  • Page 8: Installation Information

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING SHOCK The rectifier in its shipping container, withstands shock developed when one edge of the container is dropped six (6) inches while the opposite edge is resting on the ground, or it is dropped two (2) inches on any surface without any physical damage or degradation of the electrical performance.
  • Page 9: Power Cabling Formulas

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING TABLE 2 POWER CABLING FORMULAS The following section may be used to calculate the wire size requirements for wire lengths in excess of 10 ft. (Refer to TABLE 3) CMA= CROSS SECTION OF WIRE IN CIRCULAR MILS.
  • Page 10: Electrical Connections & Field Wiring

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING COPPER WIRE (KS5482-01) WIRE SIZE REQUIRED CMA = (A*LF*K) / AVD CURRENT CAPACITY (IN AMPS) (SEE TABLE 3) MAX AMPS = (CMA* AVD)/(LF*K) 8.0 ELECTRICAL CONNECTIONS & FIELD WIRING Terminal blocks are provided for connecting the a.c. input and d.c. output. A ground wire must be connected to the unit’s case ground.
  • Page 11: Operation

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING REMOTE VOLTAGE SENSING Provisions for remote d.c. voltage sensing are provided. To use the remote sensing circuit remove the wire from the positive d.c. output terminal to the RS+ terminal strip. Connect a #14 gauge wire from the RS+ terminal to the positive battery terminal.
  • Page 12: Circuit Descriptions

    11.0 CIRCUIT DESCRIPTIONS 11.1 CIRCUIT OPERATION The Model A36F-3 PHASE rectifier circuit design is a controlled ferroresonant converter. The power transformer PT provides a.c. to d.c. isolation, voltage step down, and inherent magnetic current limit. The secondary circuit of PT & capacitor C2 form a resonant tank circuit. The secondary voltage of the transformer is controlled by the shunt control which consists of choke L1 and the a.c.
  • Page 13: S2A-188 Regulator Assembly

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING In the current limit mode the triac is also fired to regulate the unit output current in the same manner. In this case, however, the unit d.c. current is being monitored, compared against the current limit set point and control is applied to the triac.
  • Page 14: Service Information

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING 5. Certain failures can be caused by defective batteries and customer loads; make sure batteries and loads are free from defects. NOTE: If the problem is found to be located in the printed circuit boards, the board should be replaced.
  • Page 15 A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING 5. Shorted C3 capacitors. 6. Loose connections on the d.c. fuse. 12.3.3 Charger operates but output voltage/current is low. Possible Cause: 1. Float/Equalize voltage potentiometers not set correctly (see float/equalize adjustment procedure for proper voltage setting).
  • Page 16: Troubleshooting And Replacing The Triac

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING 12.4 TROUBLESHOOTING AND REPLACING THE TRIAC The procedure for checking the triac is as follows: 1. On the analog ohmmeter, set the switches on “ohms”, “d.c.”, and “Rx10,000” scale. 2. Disconnect the triac to be checked. Using an ohmmeter, measure the resistance between main terminals, MT1 and MT2 in both directions.
  • Page 17 A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING 13.0 ALARM STATUS PANEL The alarm package has six (6) alarms, with eight (8) “led” lights: Blown d.c. Protection “leds” will indicate if a d.c. Protective device clears. A high & low d.c. Alarms with “led” lights (2) & relays. These alarms are preset at 2.45vdc high and 1.95vdc low.
  • Page 18: Timer Modes

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING FACTORY SETTING FOR ALARMS & TIMER MODE: LOW DC VOLTAGE - 5 SECONDS HIGH DC VOLTAGE - 5 SECONDS HIGH VOLTAGE SHUTDOWN- 20 SECONDS LOW DC CURRENT - 5 SECONDS TIMER MODE -...
  • Page 19 A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING MODE 1 DISPLAY indicates P01 § This mode of operation automatically starts an equalize cycle every 7 days. The length of this cycle is again determined by the timer setting. After the equalize period the timer will wait for another 7 days and then restart.
  • Page 20: Output Voltage

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING DIPSWITCH SETTINGS FOR ASSEMBLY S2A-178 DIPswitch – SW2 OUTPUT VOLTAGE SHUNT BAR CURRENT 100A 200A 130V 400A 800A 1600A 3200A S2A-180 DIPswitch SETTINGS – WHEN USED WITH ASSEMBLY S2A-178 Assembly S2A-180 is a multi-function relay board. There are two (2) relays on the assembly with two (2) sets of dry form “C”...
  • Page 21: Manufacturer's Warranty

    A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING MANUFACTURER'S WARRANTY All La Marche Manufacturing Co. equipment has been thoroughly tested and found to be in proper operating condition upon shipment from the factory and is warranted to be free from any defect in workmanship and material that may develop within one year from date of purchase.