Gas Pressure
Explosion
Hazard
Gas leaks can not always be detected by smell.
Gas suppliers recommend that you use a gas
detector approved by UL or CSA.
For more information, contact your gas supplier.
If a gas leak is detected, follow the "What to do if you
smell gas" instructions on the cover of this manual.
Gas Pressure
Testing
IMPORTANT: This water heater and its gas connection must be
leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a pressure
exceeding 14" W.C., the water heater and its manual shut-off
valve must be disconnected from the gas supply piping system
and the line capped.
If the gas lines are to be tested at a pressure tess than 14" W.C.,
the water heater must be isolatedfrom the gas supply piping
system by closing its manual shut-off valve.
NOTE: Air may be present in the gas lines and could prevent the
pilot from lighting on initial start-up. The gas lines should be purged
of air by a qualified technician after installationof the gas piping
system. While purging the gas piping system of air, ensure that
the fuel is not spilled in the area of the water heater installation,
or any source of ignition. If the fuel is spilled while purging the
piping system of air follow the "WHAT TO DO IF YOU SMELL
GAS" instructions on the cover of this manual.
IMPORTANT: The gas supply pressure must not exceed the maximum
supply pressure as stated on the water heater's rating plate. The
minimum supply pressure is for the purpose of input adjustment.
Table 1
Natural Gas Pipe Capacity
Table (Cu. Ft./Hr.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity
of 0.60 (natural gas).
Nominal Iron Pipe
Length of Pipe,Feet
Size,in.
10
20
30
40
50
60
70
80
90
100
125
150
175
200
1/2
132
92
73
63
56
50
46
43
40
38
34
31
28
26
3/4
278
190
152
130
115
105
96
90
84
79
72
64
59
55
1
520
350
285
245
215
195
180
170
160
150
130
120
110
100
1-1/4
1050
730
590
500
440
400
370
350
320
305
275
250
225
210
1-1/2
1600
1100
890
760
670
610
560
530
490
460
410
380
350
320
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the water heater. By formula:
Gas Input of Water Heater (BTU/HR)
Cu. Ft. Per Hr. Required=
Heating
Value of Gas (BTU/FT 3)
The gas input of the water heater is marked on the water heater data plate. The heating value of the gas (BTU/FT 3)
may be determined by consulting the local natural gas utility.