Gas Pressure
Explosion
Hazard
Gas leaks can not always be detected by smell.
Gas suppliers recommend that you use a gas
detector approved by UL or CSA.
For more information, contact your gas supplier.
If a gas leak is detected, follow the "What to do if you
smell gas" instructions on the cover of this manual.
IMPORTANT: The gas supply pressure must not exceed the maximum
supply pressure as stated on the water heater's rating plate. The
minimum supply pressure is for the purpose of input adjustment.
Gas Pressure
Testing
IMPORTANT: This water heater and its gas connection must be
leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a pressure
exceeding 14" W.C., the water heater and its manual shut-off
valve must be disconnected from the gas supply piping system
and the line capped.
If the gas lines are to be tested at a pressure tess than 14" W.C.,
the water heater must be isolated from the gas supply piping
system by closing its manual shut-off valve.
NOTE: Air may be present in the gas lines and could prevent the
pilot from lighting on initial start-up. The gas lines should be purged
of air by a qualified technician after installation of the gas piping
system. While purging the gas piping system of air, ensure that
the fuel is not spilled in the area of the water heater installation,
or any source of ignition.
If the fuel is spilled while purging the
piping system of air follow the "WHAT TO DO IF YOU SMELL
GAS" instructions on the cover of this manual.
LP Gas Only
Explosion
Hazard
Have a qualified person make sure L.P. gas pressure
does not exceed 13" water column.
Examples of a qualified person include: licensed
plumbers, authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or
fire.
Liquefied
petroleum gas is over 50% heavier than air and in
the occurrence
of a leak in the system, the gas will settle at
floor level. Basements, crawl spaces, closets and areas below
ground level will serve as pockets for the accumulation
of gas.
Before lighting an L.R gas water heater, smell all around the
appliance at floor level. If you smell gas, follow the instructions
as given in the warning on the front page.
When your L.R tank runs out of fuel, turn off the gas at ait
gas appliances
including pilot lights. After the tank is refilled,
all appliances
must be re-lit according to their manufacturer's
instructions.
Table 1
Natural Gas Pipe Capacity Table (Cu. Ft./Hr.)
Capacity
of gas pipe of different
diameters
and lengths
in cu. ft. per hr. with pressure
drop of 0.3 in. and specific
gravity
of 0.60 (natural gas).
Nominal
mron Pipe
Length
of Pipe, Feet
1/2
132
92
73
63
56
50
46
43
40
38
34
31
28
26
3/4
278
190
152
130
115
105
96
90
84
79
72
64
59
55
I
520
350
285
245
215
195
180
170
160
150
130
120
110
100
1-1/4
1050
730
590
500
440
400
370
350
320
305
275
250
225
210
1-112
1600
1100
890
760
670
610
560
530
490
460
410
380
350
320
After the length of pipe has been determined,
select the pipe size which wiB provide the minimum
cubic feet per hour
required
for the gas input rating of the water heater. By formula:
Gas Input of Water Heater
Cu. Ft. Per Hr. Required=
Heating Value of Gas (BTU/FT 3)
The gas input of the water heater is marked
on the water
heater data plate. The heating value of the gas (BTU/FT _)
may be determined
by consulting
the local natural gas utility.
Table 2
LP Gas Capacity Table
Maximum
capacity
of pipe in thousands
of BTU per hour of undiluted
liquefied petroleum
gases (at 11 inches water
column
pressure).
Based on a pressure
drop of 0.5 inch water column.
Nomina[
Iron
Pipe
Length
of Pipe, Feet
Size, in.
1(1
20
30
40
5£)
60
7Q
80
9_)
] O0
125
_50
1/2
275
189
152
129
114
103
96
89
83
78
69
63
3/4
576
393
315
267
237
217
196
185
173
162
146
132
1
1071
732
590
504
448
409
378
346
322
307
275
252
1=114
2205
1496
1212
1039
913
834
771
724
677
630
567
511
Example:
Input BTU requirement
of the water heater 100,000 BTUH.
Total pipe length, 80 feet = 3/4" IPS required.
Additional
tables are available
in the latest edition of the "National Fuel Gas Code", ANSI Z223,1,
17