Combustion Air Supply & Ventilation; Unconfined Space; Confined Space; All Air From Inside The Building - Kenmore HydroSense 153.331592 Owner's Manual

Kenmore water heater user manual
Table of Contents

Advertisement

Carbon Monoxide Warning
Follow all the local and state codes or, in the absence of
local and state codes, the "National
Fuel Gas Code",
ANSI Z223.1 (NFPA 54)- current edition to properly
install vent system.
Failure to do so can result in death, explosion,
or
carbon monoxide poisoning.
IMPORTANT:
Air for combustion
and ventilation
must not
come from a corrosive atmosphere. Any failure due to corrosive
elements
in the
atmosphere
is excluded
from
warranty
coverage.
The following types of installation (not limited to the following)
wilt require outdoor air for combustion due to chemical exposure
and may reduce but not eliminate
the presence
of corrosive
chemicals in the air:
beauty shops
photo processing labs
buildings with indoor pools
water heaters installed in laundry, hobby, or craft rooms
water heaters installed near chemical storage areas
Combustion air must be free of acid-forming chemicals such as sulfur,
fluorine, and chlorine. These elements are found in aerosol sprays,
detergents, bleaches, cleaning solvents, air fresheners, paint, and
vamish removers, refrigerants, and many other commercial and
household products. When bumed, vapors from these products
form highly corrosive acid compounds. These products should not
be stored or used near the water heater or air inlet.
Combustion and ventilation air requirements are determined by
the location of the water heater. The water heater may be located
in either an open (unconfined) area or in a confined area or small
enclosure such as a closet or small room. Confined spaces are
areas with tess than 50 cubic feet for each 1,000 BTUH of the total
input for all gas-using appliances.
Unconfined
Space
A water heater in an unconfined
space uses indoor air for
combustion and requires at least 50 cubic feet for each 1,000
BTUH of the total input for alt gas appliances. The table below
shows a few examples of the minimum square footage (area)
required for various BTUH inputs.
TABLE 2
Minimum Square
Typical Room
BTUH Input
Feet with
with 8' Ceiling
8' Ceiling
30,000
188
9 x 21
45,000
281
14 x 20
60,000
375
15 x 25
75,000
469
15 x 31
90,000
563
20 x 28
105,000
657
20 x 33
TABLE 2
Minimum Square
Typical Room
Feet with
8'
BTUH Input
8' Ceiling
with
Ceiling
120,000
750
25 x 30
135,000
844
28 x 30
IMPORTANT:
The area must be open and be able to provide the proper
air requirements
to the water heater. Areas that are being
used for storage or contain large objects
may not be
suitable for water heater installation.
Water heaters installed in open spaces in buildings with
unusually tight construction
may still require outdoor
air
to function properly. In this situation, outside air openings
should be sized the same as for a confined space.
Modern
home
construction
usually
requires
supplying
outside air into the water heater area.
Confined
Space
For the correct
and proper operation
of this water heater,
ample air must be supplied for the combustion, ventilation, and
dilution of flue gases.
Small enclosures
and confined areas
must have two permanent openings so that sufficient fresh air
can be drawn from outside of the enclosure. One opening shall
be within 12 inches of the top and one within 12 inches of the
bottom of the enclosure as shown in Figure 12.
The size of each opening (free area) is determined by the total
BTUH input of all gas utilization equipment (i.e., water heaters,
furnaces, clothes dryers, etc.) and the method by which the air
is provided. The BTUH input can be found on the water heater
rating plate. Additional air can be provided by two methods:
1.
All air from inside the building.
2.
All air from outdoors.
12" MAXIMUM
PERMANENT
OPENINGS
TO
THE OUTSIDE
OR
ADDITIONAL
ROOMS WITHIN
THE BUILDING
I
12" MAXIMUM
J
CLOSET
4:
OR
--
OTHER
CONFINED
SPACE
FIGURE 12.
All Air from Inside the Building
16
When additional
air is to be provided to the confined
area
from additional room(s) within the building, the total volume of
the room(s) must be of sufficient size to properly provide the
necessary
amount of fresh air to the water heater and other