Slant/Fin B-120A Installation And Operating Instructions Manual page 33

Direct-vent sealed combustion condensing boiler hot water gas-fired boilers for natural and l.p. propane gases
Hide thumbs Also See for B-120A:
Table of Contents

Advertisement

Bobcat Models B-120A and B-200A
The menu is accessed by pressing and holding "SELECT" and "ENTER" buttons for 10 seconds. To change
WARNING: Only a trained, experienced service technician or installer should use this table.
MODE DISPLAY
*
*
*
*
*
*
*
**
*
*
**
*
NOTE:
*: Alternating **: Steady
VIEWING AND CHANGING SYSTEM SETTING - Table 5
Temperature Display is in Farenheit only
"To change system setting or perform system test"
system setting: Press "UP or DOWN" button, then press "ENTER"
Press "SELECT" to go to next menu setting
Changing space heating post pump time. Settable from 10 to 900 seconds.
*
Changing DHW post pump time. Settable from 1 to 255 seconds.
*
*
*
Boiler model selection, value is 0 for model B-120A and 4 for model B-200A
*
Boiler model confirmation, value is 0 for model B-120A and 4 for model B-200A
Weather compensation supply water reference temperature
(space heating mode 1 or 2). Settable from 16°F to 122°F (steps of 1 F).
Changing compensation slope (space heating mode 1 or 2).
Changing weather compensation set point (space heating mode 2 only).
Display shows blower RPM (mutiply reading by 10 for actual RPM)
Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).
Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).
DESCRIPTION
(steps of 10 seconds). The default value is 30 seconds.
(steps of 1 seconds). The default value is 15 seconds.
Changing space heating control mode
0: Thermostat only (default) - boiler without outdoor sensor
1: Outside sensor and Thermostat
2: Outside sensor only
3: Permanent heat demand (boiler circulator always on)
Changing domestic hot water (DHW) mode
0: No DHW
1: Storage tank with sensor
2: Storage tank with thermostat (default value)
3: Plate heat exchanger
Changing DHW or space heating priority mode
0: DHW priority (no time limit)
1: Space heating priority (no time limit)
2: DHW priority for limited time (default)
3: Space heating priority for limited time
Changing priority limited time. Settable from 20 to 80 minutes.
The default value is 30 minutes.
The default value is 86°F .
Settable from 0.1 to 5.0 (steps of 0.1).
The default value is 1.0.
Not Utilized
Settable from 32°F to 122°F (steps of 1°F).
The default value is 68°F .
Display shows flame current in micro amps
System test – Display shows flame current
0: System test off
L: Steady low input (20 minutes)
I: Steady ignition input (20 minutes)
H: Steady high input (20 minutes)
33