Slant/Fin EUTECTIC EC10DV Series Installation Instructions Manual

Direct vent oil-fired water boiler
Hide thumbs Also See for EUTECTIC EC10DV Series:

Advertisement

EUTECTIC EC10DV
INTREPID
DIRECT VENT OIL-FIRED WATER BOILER / NO.2
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Basic Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Installing the joint assembly . . . . . . . . . . . . . . . . . . . . . . . .4
Outside Terminal
Installing the outside terminal . . . . . . . . . . . . . . . . . . . . .5
Connections to the outside terminal . . . . . . . . . . . . . . . .6
Connections to appliance . . . . . . . . . . . . . . . . . . . . . . . . . .7
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Vent system part numbers . . . . . . . . . . . . . . . . . . . . . . . . . .8
Alternate Field Controls Vent Terminal . . . . . . . . . . . . . .8-14
Slant/Fin TR SERIES, models TRDV are approved for instal-
lation as a direct vent system. The following basic guidelines
should be observed according to the venting system in use.
In addition, it is strongly recommended that the applicable
precautions for Natural Draft Applications be used.
FLEX-L DATA APPLIES TO TRDV SERIES ONLY.
FIELD CONTROL DATA APPLIES TO BOTH TRDV SERIES AND EC10DV SERIES.
In addition to all the pertinent information regarding Natural
Draft Applications whenever a Mechanical Draft Application is
used it should be installed using the following instructions and
Figures 2 and 3 as reference.
• The terminating vent hood, and the inlet air hood are on
the same wall surface. and are on the wall opposite from
the prevailing wind wall, if possible.
• All of the air for combustion to the burner is supplied
directly from the outside of the building or structure.
• Not less than 12 in. above the total accumulated
snow and level grade.
• Not less than 4 ft. horizontally or below any
window, and door or air inlet and also not less than
1 ft. above any of these openings.
• Not less than 3 ft. above a powered air inlet
device that is within 10 ft.
• Not less than 2 ft. from any other building.
TRDV Series
VENTING INSTALLATION INSTRUCTIONS
Installation Considerations
Series /
DO NOT DESTROY
THESE INSTRUCTIONS MUST
REMAIN WITH EQUIPMENT
• At least 3 ft. from any inside corner of a building
• At least 1 ft. from any roof soffit or ridge vent.
• At least 7 ft. above any public walkway.
• All of the vent construction consists of suitable materials,
and terminates at an approved stainless steel hood.
• All of the vent piping must be sealed from air leaks.
• The vent pipe bend radius is 12 in.
• Brace metal strapping every 36 in. to support
vent pipe and prevent it from sagging.
• Follow the national codes for the installation of oil burning
equipment in USA-NFPA 31, in Canada CAN/CSA - B139
and local regulations.
PUBLICATION NO. TRDV/ECDV40-V
Printed in Canada 04/08
Part No. 43-2770

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin EUTECTIC EC10DV Series

  • Page 1: Table Of Contents

    Alternate Field Controls Vent Terminal ....8-14 DO NOT DESTROY Slant/Fin TR SERIES, models TRDV are approved for instal- THESE INSTRUCTIONS MUST lation as a direct vent system. The following basic guidelines REMAIN WITH EQUIPMENT should be observed according to the venting system in use.
  • Page 2: Application (Flex-L Vent Terminal) Direct Vent Applications

    TRDV SERIES...
  • Page 3 Moisture and ice may form around terminal. Make sure the surface is in good repair and protected from damage. Only Slant/Fin models TRDV boilers can be installed on sealed or direct vented systems. They must be ordered from the factory with an approved Direct Vent System.
  • Page 4: Installing The Joint Assembly

    TRDV SERIES FIGURE 4: Joint assembly INSTALLING THE JOINT ASSEMBLY should be fully inserted into the inner vent tube until it’s tight. The seams of both tubes must be aligned for ease of insertion. 1. Loosen the gear clamps attached to the adapter sleeve and If the adapter does not completely screw into the vent pipe, slide the adapter sleeve over the vent pipe, Figure 4 and unscrew it and try again as per Step #4.
  • Page 5: Installing The Outside Terminal

    TRDV SERIES INSTALLING THE OUTSIDE TERMINAL The maximum wall thickness shall be no more than 356mm (14 in). Contact Slant/Fin for recom- mendation in case of a thicker wall. The system is not designed for common venting. Use for a single appliance only.
  • Page 6: Connections To The Outside Terminal

    TRDV SERIES CONNECTIONS TO THE OUTSIDE TERMINAL 7. Slide the inner section over the outer section and secure by tightening the gear clamp. Use Figure 8 and Figure 9 to complete the following steps. 8. Air intake piping is field supplied and must be installed 1.
  • Page 7: Connections To Appliance

    TRDV SERIES CONNECTIONS TO APPLIANCE 7. Air intake piping is field supplied and must be installed accord- ing to local code requirements. Galvanized flue pipe or Flex L Using Figures 10 and 11 complete the following steps: air intake piping can be used. For optional Flex L air intake pip- 1.
  • Page 8: Maintenance

    TRDV SERIES FIGURE 15: Vacuum relief valve FIGURE 14: Connection of vacuum relief valve MAINTENANCE For the appliance see the installation manual, TRDV-40, for the required maintenance. The vent system must be checked annually by a qualified heating professional. Vent system must be sealed and the intake and exhaust opening clear of any obstructions. VENT SYSTEM PART NUMBERS S/F Part Item...
  • Page 11 EC10DV SERIES ITEMS INCLUDED IN KIT: FIELD DIRECT VENT SYSTEM FDVS Direct Vent Termination *VRV-4 Vacuum Relief Valve Backing Plate Installation Instruction Sheet **Bagged Hardware **Cover Ring **Cover Sleeve **Appliance Adapter **Adapter Clamp *Not included in some models **Included with FOVP (Flex Oil Vent Pipe) for some models Model: FDVS The Field Direct Vent System (FDVS) is a non-powered positive pressure side wall vent termination system for use only with...