Clearances To Combustibles; Clearances; Alcove Installations - Warmland PS45 Classic Series A Installation And Operating Instructions Manual

Warmland pellet stove model ps45 classic series a
Table of Contents

Advertisement

3"
Fig #3b Right Wall - Horizontal Vent
*See Vent Manufacturer's
instructions
Fig #3c Right Wall - vertical vent
6"
Fig #3d Alcove Installation
NOTE: INSTALL VENT
A T
C L E A R A N C E S
S P E C I F I E D BY T H E
VENT MANUFACTURER
PELLET STOVES
3"
Fig# 3a Corner Install
3"
6"
3"
24"
6"

Clearances to Combustibles

Clearances:

Front
48" (1.2m)
Side
6" (155mm)
Back
3" (76mm)
The center of the fl ue is 16-1/2" above the surface upon
which the stove rests.
IMPORTANT
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT
MANUFACTURER.
• Minimum clearances specifi ed may not allow for ease of
operation and maintenance (please take this in to account when
planning the installation). If installed to the minimum clearances,
removal of the appliance may be necessary for servicing.
• Recommended clearance zone from the front
of the appliance to combustibles is 4 feet minimum.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO
SCALE.

Alcove Installations

Minimum alcove height is 5 ft. (1.54 m), minimum width is 36
in. (92 cm) and maximum depth is 24 in. (61 cm).
Note, it is difficult to service the unit when installed
in a 36 in. alcove and may require the unit to be
removed for servicing. Please allow as much area
on either side of the unit as possible for ease of
service.
7
PS45 CLASSIC 151211-24