8. Summary table of thermostat parameters

Function
Multi-function input
External temperature probe
Nighttime Reduction
Limitation
Temperature control mode
Control algorithm
Hysteresis (ON/OFF)
Proportional band (PID)
Integral period (PID)
Unit of measurement (tem-
perature)
Temperature offset
PIN number
Temperature set-point
Table 1. Device parameters

9. Alarms

The thermostat is capable of displaying an alarm condition associated with the use of the external temperature
probe as described in subsection 7.6.
Parameters
Value range
[Off, Nighttime
Reduction,
IN selection
Activation,
Heating/Air-Con.]
[Off, View,
EXT Probe se-
Temperature
lection
Limitation]
δ
(red. offset)
R
T
(Temp. limit)
[30,..,50]°C
L
Selection
[Heat., Air-con.]
TempCtrl
Algorithm
[ON/OFF, PID]
δ
(Differential)
[0.1,..,1]°C
T
Band
[0.5,..,5]°C
Period
[10,..,30] minutes
Temperature unit
TE (Offset temp.)
[0,..,±3]°C
Pin
[000,..,999]
T
(Man Heat.)
[10,..,35]°C
M
T
(Man Air-Con.)
[10,..,35]°C
M
T
(Comfort Heat.)
[10,..,35]°C
2
T
(Comfort Air-
2
[10,..,35]°C
Con.)
T
(No Heat.)
[TG,10,..,35]°C
0
T
(No Air-Con.)
[10,..,35,OFF]°C
0
T
(Antifreeze)
[4,..,10]°C
G
Resolution
-
-
Control,
[1,..,6]°C
0.1°C
0.1°C
-
-
0.1°C
0.1°C
1 min
[°C , °F]
-
0.1°C
1
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
Default value
Off
Off
4°C
35°C
Heating
ON/OFF
0.2°C
1°C
20 min
°C
0°C
000
18°C
26°C
20°C
25°C
16°C
29°C
5°C
21