Kenmore POWER MISER 153.33616 Owner's Manual page 10

30/40 gallon short 30/40/50 gallon high altitude 30/40/50 gallon 30/40/50 gallon propane (lp.) 40/50 gallon propane (l.p.) high altitude
Table of Contents

Advertisement

Breathing
Hazard - Carbon
Monoxide
Gas
S
Install water heater in accordance
with the instruction
manual
and
NFPA 54.
To avoid injury, combustion
and
ventilation air must be taken from
outdoors.
Do not place
chemical
vapor
emitting
products
near water
heater.
Breathingcarbon monoxide can cause brain damage or
death. Always read and understand instruction manual
A gas water heater cannot operate properly without the correct
amount of air for combustion, see Figure 9. Do not install in a
confined area such as a closet, unless you provide air as shown
in the Locating The New Water Heater section.
Never obstruct
the flow of ventilation air. If you have any doubts or questions at
all, call your gas supplier.
Failure to provide the proper amount
of combustion air can result in a fire or explosion and cause
death, serious bodily injury, or property damage.
12" MAX. (305 mr¢
1
VENTILATION
AIR
OPENING
O
{
13Q5 m ini
FRONT
VIEW
_
OF DOOR
AIR DUCT
FIGURE9.
If this water heater will be used in beauty shops, barber shops,
cleaning
establishments,
or self-service
laundries
with dry
cleaning equipment,
it is imperative that the water heater or
water heaters be installed so that combustion and ventilation
air be taken from outside these areas.
Propellants
of aerosol
sprays
and volatile
compounds,
(cleaners,
chlorine
based chemicals,
refrigerants,
etc.) in
addition to being highly flammable
in many cases, will also
change to corrosive
hydrochloric
acid when exposed
to the
combustion products of the water heater.
The results can be
hazardous,
and also cause product failure.
Insulation
Blankets
Insulation blankets available to the general public for external
use on gas water heaters are not necessary
with Kenmore
products. The purpose of an insulation blanket is to reduce the
standby heat loss encountered with storage tank heaters, Your
Kenmore water heater meets or exceeds the National Appliance
Energy Conservation
Act standards with respect to insulation
and standby loss requirements,
making an insulation blanket
unnecessary.
Breathing
Hazard
- Carbon
Monoxide
Gas
....
. :-'._,.,
• Do not obstruct water heater air
_'¢ :S.
intake
with
insulating
blanket.
i_i',"_i" • Gas and carbon monoxide
• detectors are available,
_
_
lni_thal_-Wltne.rthe(?_er inmaCCa°_dance
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual
_i&
WARNING
Should you choose to apply an insulation blanket to this heater,
you should
follow
these
instructions
(See
Figure
1 for
identification of components mentioned below). Failure to follow
these instructions
can restrict the air flow required for proper
combustion,
potentially resulting in fire, asphyxiation,
serious
personal injury or death.
Do not apply insulation to the top of the water heater, as this
will interfere with safe operation of the draft hood.
Do not cover the outer door, thermostat or temperature
&
pressure relief valve.
Do not allow insulation to come within 2" (50.8 mm) of the
floor to prevent blockage of combustion air flow to the burner.
Do not cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.
Do obtain new warning and instruction
labels from Sears
for placement on the blanket directly over the existing labels.
Do inspect the insulation blanket frequently to make certain
it does not sag, thereby obstructing combustion air flow.
10
Combustion
Air and Ventilation
for
Appliances
Located
in Unconfined
Spaces
UNCONFINED
SPACE is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 m 3 per kW) of the
aggregate input rating of all appliances installed in that space.
Rooms communicating
directly
with the space in which the
appliances
are installed, through openings not furnished with
doors, are considered a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion,
ventilation
and dilution of flue
gases.
However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.),
additional
air may need to be provided
using the methods
described
in Combustion
Air and Ventilation
for Appliances
Located in Confined Spaces.