Hide thumbs Also See for CS-F14DB4E5:
Table of Contents

Advertisement

TABLE OF CONTENTS

1 Service Information---------------------------------------------- 3
1.2. Caution of test operation--------------------------------- 3
1.4. Operation range-------------------------------------------- 4
CS-F14DB4E5 CU-J14DBE5
CS-F18DB4E5 CU-J18DBE5
PAGE
2 Features--------------------------------------------------------------5
2.1. Cassette Type features -----------------------------------5
2.2. Outdoor Unit ------------------------------------------------5
2.3. Wired Remote Control ------------------------------------7
2.4. Wireless Remote Control --------------------------------7
© 2006 Panasonic HA Air-Conditioning (M) Sdn Bhd
(11969-T). All rights reserved. Unauthorized copying
and distribution is a violation of law.
Order No. MAC0602017C2
Air Conditioner
PAGE

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CS-F14DB4E5

  • Page 1: Table Of Contents

    1.3. Caution during automatic address setting----------- 3 2.3. Wired Remote Control ------------------------------------7 1.4. Operation range-------------------------------------------- 4 2.4. Wireless Remote Control --------------------------------7 © 2006 Panasonic HA Air-Conditioning (M) Sdn Bhd (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.
  • Page 2 3.3. Safety Devices -------------------------------------------- 11 13.8. Operating characteristics ----------------------------- 110 4 Dimensions ------------------------------------------------------- 12 14 Exploded View (Indoor Unit) ------------------------------- 111 4.1. CS-F14DB4E5 CS-F18DB4E5 ---------------------- 12 14.1. CS-F14DB4E5 CS-F18DB4E5 ---------------------- 111 4.2. CU-J14DBE5 CU-J18DBE5 -------------------------- 13 14.2. CS-F14DB4E5 CS-F18DB4E5 ---------------------- 112...
  • Page 3: Service Information

    1 Service Information Notice of Address setting for NEW Cassette / NEW Outdoor Unit. The new Cassette / New Outdoor models are possible to have address setting for twin control or group control by auto- matic when main power supply is switched on. (Manual address setting is also possible by using Dip switch on Indoor unit P.C.
  • Page 4: Operation Range

    1.4. Operation range 1.4.1. Power Supply The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be bal- anced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage.
  • Page 5: Features

    2 Features 2.1. Cassette Type features 2.1.1. Three Airflow Patterns for Extra Comfort • Multi-comfort air control. 2.1.2. Low Noise and High Air Flow Rate • The cassette indoor unit is equipped with newly-develop turbo fan; the new shape produces low noise and high air flow rate. 2.1.3.
  • Page 6 • Centralized Drain Method gathered multiple outdoor unit’s drain pipes into a single drain pipe to make installation easier and also improve appearance. • Side-by-Side Continuous Installation is possible even outdoor units with different capacities. 2.2.2. Quiet, Efficient Design • A host of silencing technologies achieves super-quiet operation. •...
  • Page 7: Wired Remote Control

    2.3. Wired Remote Control 1. The new design includes an easily-visible red pilot lamp. The power can be turned on and off at a single touch, without open- ing the cover. 2. Has a build-in thermistor, allowing indoor temperature detection in accordance with indoor conditions by switching with main unit thermistor.
  • Page 8: Group Control Equipment

    2.5. Group Control Equipment Group control by one remote control [Remote side] • All air conditioner units are controlled • Optional wired remote as a whole by remote control. control CZ-RD513C • All indoor units operate in the same mode. [Local side] Not needed Wired...
  • Page 9: Product Specification

    3 Product Specification 3.1. CS-F14DB4E5 CU-J14DBE5 ITEM / MODEL Indoor Unit Outdoor Unit Main Body CS-F14DB4E5 CU-J14DBE5 Panel CZ-BT03P Remote CZ-RD513C (Wired) Control CZ-RL513B (Wireless) Cooling Capacity BTU/h 13,000 Refrigerant Charge-less Standard Air Volume for High, /min 1942 Outside Dimension (H x W x D)
  • Page 10: Cs-F18Db4E5 Cu-J18Dbe5

    Single Power Consumption Cooling 1.69 1.72 1.75 Running Current Cooling 7.75 7.70 7.65 Starting Current Power Factor Cooling *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 11: Safety Devices

    3.3. Safety Devices INDOOR UNIT Indoor Unit Heat Pump Model CS-F14DB4E5 CS-F18DB4E5 Cooling only Model For fan motor current protection Internal control board (note) 1.15 1.15 For control protection Fuse 3.15 3.15 note: protection controlled by P.C.B installed of FM inside...
  • Page 12: Dimensions

    4 Dimensions 4.1. CS-F14DB4E5 CS-F18DB4E5...
  • Page 13: Cu-J14Dbe5 Cu-J18Dbe5

    4.2. CU-J14DBE5 CU-J18DBE5...
  • Page 14: Refrigeration Cycle

    5 Refrigeration Cycle 5.1. CS-F14DB4E5 CU-J14DBE5...
  • Page 15: Cs-F18Db4E5 Cu-J18Dbe5

    5.2. CS-F18DB4E5 CU-J18DBE5...
  • Page 16: Block Diagram

    6 Block Diagram 6.1. CS-F14DB4E5 CS-F18DB4E5 6.2. CU-J14DBE5 6.3. CU-J18DBE5...
  • Page 17: Wiring Diagram

    7 Wiring Diagram 7.1. CS-F14DB4E5 CS-F18DB4E5...
  • Page 18: Cu-J14Dbe5

    7.2. CU-J14DBE5...
  • Page 19: Cu-J18Dbe5

    7.3. CU-J18DBE5...
  • Page 20: Operation Instructions

    8 Operation Instructions 8.1. Wired Remote Control (Optional part) Name and function of each part Airflow direction setting display OFF/ON button Used to start and stop the operation. FAN SPEED button Used to select the fan speed of high (HI), medium (MED), low (LO) or auto (AUTO).
  • Page 21: Remote Control - Display

    8.2. Remote Control - Display...
  • Page 22: Remote Control - Panel

    8.3. Remote Control - Panel...
  • Page 23: How To Set Remote Control Day And Time

    8.4. How to set remote control day and time • The day and time needs to be set when you turn on the power for the first time or after a long time has elapsed since the power was last turned on. •...
  • Page 24: Daily Timer Setting

    CLOCK Display (To set current Day and Time) Note: • The above display is shown if no valid timer setting is made. • If valid timer setting is made. and setting will be displayed. - If you want to check the current time and day, press “MODE button” once. (However, after a few seconds, the display will change back to and the setting) 8.6.
  • Page 25: Weekly Timer Setting

    Final Display of Daily Timer: 8.7. Weekly Timer Setting • Display • How to Set Weekly Timer - You can set the Timer for 1 week (Monday to Sunday) with 6 programs per day. - ON-Timer can be set together with your desired temperature. However, this temperature will be used continuously. - Cannot set 2 programs with same time setting in a day.
  • Page 26 For example , if you want to set: A - Monday to Friday: Same time, 1st program ON 9:00 & 2nd program OFF 16:00. B - Only Wednesday: Additional 3rd program OFF 12:30 & 4th program ON 13:30. C - Only Saturday: 1st program ON 10:00 with 20°C & 2nd program OFF 14:00. D - Sunday: Holiday.
  • Page 27: Wireless Remote Control (Optional Part)

    8.8. Wireless Remote Control (Optional part) Name and function of each part Time/time setting display Shows the timer operation setting time or the current time. Address number display Operation selection display OFF/ON button Used to start and stop the operation. ODOUR WASH button FILTER RESET button Press to cancel the “FILTER”...
  • Page 28: Operation Details

    9 Operation Details 9.1. Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • Cooling Operation Time Diagram. 9.2.
  • Page 29: Normal Control

    9.5. Normal Control 9.5.1. Cooling Indoor Fan Control • Manual Fan Speed Operation starts at High, Medium or Low speed set by remote control. • Auto Fan Speed When operation start, or shifting to thermostat ON condition from thermostat OFF condition, indoor fan operates as below. Thermostat &...
  • Page 30: Operation Control

    9.5.3. Cooling Outdoor Fan Control • During cooling operation, outdoor fan speed changes according to outdoor pipe temperature. • The fan speed is controlled by the timing of turning the outdoor fan ON and OFF within an interval. • When outdoor pipe temperature increase, interval timing increased. •...
  • Page 31: Energy Saving

    9.6.3. Energy Saving • During Operation, press "Economy" button at remote control to enable Energy Saving Operation. • The air conditioner judges the stable condition, where the different between indoor suction temperature and setting temperature is 1°C for 30 minutes and moderately shifts the set temperature in 0.5°C steps (Maximum 2°C) to control energy saving opera- tion.
  • Page 32: Thermostat Control

    9.6.9. Pump-down Control • To enable pump down operation, at outdoor PCB, set the DS1 to OFF position. • Press Test Run button for 1 second. • During Pump Down operation, push the Test Run button again for 1 second to stop the pump down operation. •...
  • Page 33: Protection Control

    9.7. Protection Control 9.7.1. Outdoor Low-pressure Protection Control • The purpose of low-pressure protection control is gas leakage detection control. • The low-pressure protection control starts when low-pressure switch is activated less than 15 minutes after compressor startup. • During this protection control, compressor is shut down, indoor unit is set to thermo-off status. •...
  • Page 34: Test Run

    9.7.8. High-pressure Switch Disconnection Error Detection Control • High-pressure switch disconnection is detected when high-pressure switch input continuously open for 1 minutes while the com- pressor shutdown. • During this error, high-pressure switch error is displayed. 9.7.9. Low-pressure Switch Disconnection Error Detection Control •...
  • Page 35: Installation Instruction

    Liquid / Valve Gas / Valve Max(m) Max(m) Max(m) Max(m) (g/m) High Cassette R410A CS-F14DB4E5 6.35 3-ways 12.70 3-ways type CS-F18DB4E5 Note : Piping elevation B = outdoor unit installed at top Piping elevation C = outdoor unit installed at bottom...
  • Page 36: Refrigerant Additional Charge

    10.2. Refrigerant additional charge 1. Piping installation by standard piping • At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 20 m. (Refer the following table) But when the piping length exceeds 20m, additional charge is required according to the following table. Example: CU-J14DBE5 In case of 30m long pipe (one way), the amount of refrigerant to be replenished is: (30 - 20) x 20 = 200g...
  • Page 37: Indoor Unit Installation

    10.4. Indoor unit installation FOUR WAY CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS Precautions in terms of safety Carry out installation work with reliability after thorough reading of this “Precautions in terms of safety”. • Precautions shown here are differentiated between Warnings and Cautions.
  • Page 38 Warnings When performing piping work do not mix air except for specified Installation of Earth Leakage Current Breaker refrigerant (R22) in refrigeration cycle. it causes capacity down, This equipment must be installed with earth leakage and risk of explosion and injury due to high tension inside the current breaker.
  • Page 39: Installation Of Indoor Unit

    10. Do not install the indoor unit at a laundry. Electric shocks may result. NOTE • Thoroughly study the following installation locations. 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying, dispersing of water drops, drain pump malfunction, etc.
  • Page 40 POSITIONS OF AIR CONDITIONER BODY AND CEILING SURFACE Tighten the nuts and bolt to prevent unit from falling. Warning HANGING POSITION OF THE AIR CONDITIONER BODY Air conditioner body gap setting between ceiling surface should be 10mm as right figure. (Adjustment of height direction should be done after fixing decorative panel.)
  • Page 41: Refrigerant Piping

    10.4.4. Refrigerant piping Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit.(Additional charging, etc.) 1. Brazing for piping. a. Execute brazing before tightening the flare nut. b. Brazing must be executed while blowing nitrogen gas. (This prevents generation of oxidized scale in copper pipe.) 2.
  • Page 42: Heat Insulation

    Heat insulation material: Polyethylene foam with thickness more than 8mm (local supply). Drain Test The air conditioner uses a drain up motor to drain water. Use the following procedure to test the drain up motor operation. • Connect the main drain pipe to exterior and leave it provisionally until the test comes to an end. •...
  • Page 43: Electrical Wiring

    2. Precautions in high humidity circumstance. This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been confirmed that there are no faults. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall.
  • Page 44 CONNECTING THE WIRES TO THE CONTROL BOX • Remove the mounting screw, remove the control box cover, and then connect the wires by following the procedure given in the illustration. Caution Make sure that screws of the terminal are securely tightened. Earth lead wire shall be longer than other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from anchorage.
  • Page 45: Installation Of Decorative Panel

    10.4.8. Settings Do not operate the remote controller within 1 minute after turning on the power of the indoor unit. When using group control with the standard type, at least 1 unit must be set at No.1 at the indoor unit. Check the settings of the indoor unit in a case where there are no display at remote controller.
  • Page 46 2. Remove the corner cover in 4 corner places. Pull hook of corner cover as direction , at same time remove it by sliding out in direction 3. Fix the hanger (2 pieces) of the decorative panel to the indoor unit. There is direction information at decorative panel [PIPING SIDE] indication meaning the direction of piping side.
  • Page 47 6. Adhere the cosmetic panel and ceiling wall together and corfirm no gap in between. Readjust indoor unit height, if there is a gap between ceiling wall and decorative panel although it have been fixed by screw. If there are no effect to the indoor unit level and drain piping etc., the adjustment of indoor unit height can be adjusted through the corner hole.
  • Page 48 10.4.10. As for timer output • Connect the timer cord to connector (CN-TIMER) on print circuit board. 10.4.11. Precautions in test run • The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner may not operate. •...
  • Page 49: Hand Over

    10.4.12. Check the following items when installation is complete • After completing work, be sure to measure and record trial run properties, and store measuring data, etc. • Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind vol- ume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure, airtight pressure.
  • Page 50: Outdoor Unit Installation

    10.5. Outdoor unit installation AIR CONDITIONERS OUTDOOR UNIT INSTALLATION INSTRUCTIONS Precautions in terms of safety Carry out installation work with reliability after thorough reading of this “Precautions in terms of safety”. • Precautions shown here are differentiated between Warnings and Cautions.
  • Page 51 Warnings The unit must be installed in accordance with applicable national Once installation work is completed, check that there are no refrig- and local regulations. erant gas in the room that can come into contact with sparks or Any electrical work should only be carried out by qualified techni- flames from a fan heater, stove or kitchen range, which will cause cian and use exclusive circuits without fail.
  • Page 52 2. Installation work a. Brazing work Brazing work needs replacing air inside pipe with nitrogen gas in order to prevent oxidation scale from occurring. This is called nitrogen replacement, and one of very important work in brazing refrigerant piping. (Oxidation preventive is not possible to use) b.
  • Page 53 4. Refrigerant filling Refrigerant filling must be done in the state of liquid refrigerant. If this is done in gas refrigerant, the balance of refrigerant composition will collapse and damage the operation. For the use of a gas cylinder without siphon inside, turn it upside down and use it. (We recommend manifold with sight glass.) Do not use a “CHARGE CYLINDER”.
  • Page 54 1. There should be sufficient ventilation. 2. The outdoor unit should be sheltered as much as possible from rain and direct sunlight, and the air should be able to move around so that hot and cold air do not build up. 3.
  • Page 55 10.5.5. Transporting and installing the outdoor unit • Transporting 1. The outdoor unit should be transported in its original packaging as close to the installation location as possible. 2. If suspending the outdoor unit, use a rope or belt, and use cloth or wood as padding in order to avoid damaging the unit. •...
  • Page 56 2. Local pipes can project in any of four directions. • Make holes in the pipe panels for the pipes to pass through. • Be sure to install the pipe panels to prevent rain from getting inside the outdoor unit. [Removing the service panel].
  • Page 57: Charging With Refrigerant

    10.5.7. Heat insulation Use a material with good heat-resistant properties as the Liquid-side pipes Material that can withstand heat insulation for the pipes. Be sure to insulate both the Gas-side pipes 120°C or higher gas-side and liquid-side pipes. If the pipes are not ade- Caution quately insulated, condensation or water leakages may occur.
  • Page 58 Connect the power supply line to a 3-phase/380-415V (or single-phase 220-240V) power supply. The equipment shall be connected to a suitable mains network with a main imped- ance less than the valve indicated in the table of power supply specifications. Be sure to connect the wires correctly to terminal board with connecting the crimp type ring terminal to the wires.
  • Page 59 • Power supply specifications Circuit breaker Indoor/outdoor Leakage (Minimum Capacity) Minimum Maximum unit connection current power permissible power cables cable Model name impedance breaker Switch Fuse supply based on (terminals (Ω) cables length (m) CU-B14DBE5 CU-J14DBE5 220V-240V~ 0.0374 CU-B18DBE5 CU-J18DBE5 220V-240V~ 0.0374 CU-B24DBE5...
  • Page 60 10.5.11. Precautions with regard to test operation • Use only insulation tool to the switch on the microswitch on the electric circuit board. (Do not use finger or a metallic object.) • Do not switch on power before all installation is completed. •...
  • Page 61 10.5.12. As to making the inspection after completion of work fully understood • At the time when the work has been completed, measure and record the characteristics of test run without fail and keep the mea- suring date, etc. • Carry out the measurement regarding room temperature outside air temperature, suction and air discharge temperatures, wind velocity, wind volume, voltage current, presence of abnormal vibration, operating pressure, piping temperature, compressive pressure, airtight pressure as items to be measured.
  • Page 62: Wired Remote Control Installation

    10.6. Wired remote control installation Wired Remote Control Installation Manual • Before installing the wired remote controller, be sure to thoroughly read the “Notes with regard to safety” section of the installa- tion manual provided with the indoor unit. • After installing the wired remote controller, carry out a test operation to check that the remote controller functions properly, and also explain the operation and cleaning procedures to the customer in accordance with the details in instruction manual.
  • Page 63 Remote controller wiring • Connect the indoor unit and the remote controller as shown in the illustration below. • The remote control cable is non-polar. • At the time of shipment from the factory, the connector cable used to connect the terminal block and connector CN1 is discon- nected.
  • Page 64 • If installing the remote controller with the remote control cable exposed, use pliers to cut a notch into the upper case. (The feed- ing-out direction can be either up or to the left or right) • Strip the end of the remote control cable which is to be connected to the remote controller. (Refer to the illustration below) •...
  • Page 65 If remote control cable is embedded If installing with the remote control cable exposed 1. Embed an outlet box (JIS C 8336) into the wall, and then secure 1. Secure the remote controller base plate to the wall with two acces- the remote controller base plate to the outlet box with the two sory 4 mm screws.
  • Page 66 10.6.4. Settings Control using two remote controllers • Up to two remote controllers can be installed for a single indoor unit, and either remote controller can be used to operate the indoor unit. • The indoor unit can be operated with the last switch pressed having priority. 1.
  • Page 67 Automatic address resetting for group control • The address settings for group control (air conditioner Nos. 1 to 16) can be reset automatically. 1. When operation is stopped, press for 5 seconds, continue the TEST RUN switch to display “00” (will be LOCAL MODE). 2.
  • Page 68: Test Operation

    10.6.5. Test operation • Turn on the main power. • After 3 minutes have passed since the power was turned on, press the OFF/ON switch on the remote controller. (No operation occurs within 3 minutes after the power was turned on.) •...
  • Page 69 Example of previous problem display Example of abnormality display before previous display • The display can be switched between the previous problem and the one before that by pressing the UP (TIMER) DOWN (TIMER) switches. • After eliminating the cause of the problem, press the CHECK switch once more to return to the normal display.
  • Page 70: Wireless Remote Control Installation Manual

    10.7. Wireless remote control installation manual Wireless Remote Control Installation Manual • Before installing the wireless remote controller, be sure to thoroughly read the “Notes with regard to safety” section of the instal- lation manual provided with the indoor unit. •...
  • Page 71 Attach the receptor unit onto the decorative panel of the indoor unit as shown in the figure below. 1. Remove the “corner cover” at the decorative panel indicate “Panasonic” logo left side. 2. Attach the receptor unit which same position.
  • Page 72 1. Route the joint cord for wiring as shown in the figure (figure of the back of decorative panel) below. Pass the cord through the hook of the decorative panel, taking care that the cord does not run on the heat insulator, etc. 2.
  • Page 73 Receptor unit (for ceiling type) assembly procedure Attach the receptor unit onto the indoor main unit as shown in the figure below. Remove the air-intake grille and the side cover. To remove the side cover, remove the fixing screw each on the left and the right and pull the side cover towards you. (Refer to the installation Manual supplied with the indoor main unit.) Remove the Decorative grille (component on which the brand name is shown) to the right on the air-blow opening.
  • Page 74 Route the joint cord for wiring and connect it to P.C.B terminal <CN-DISP> in the control box of the indoor unit. 1. Route for wiring the cord as shown in the figure to the right. 2. Remove the control box cover by removing the two fixing screws and connect the joint cord to P.C.B terminal <CN-DISP> in the control box.
  • Page 75 NOTE • If the batteries are replaced or the remote controller is reset, the address setting will return to ADDRESS1, so you will need to repeat the address setting again. All setting details which are stored in memory will be cleared, so you will need to repeat the setting. •...
  • Page 76 [Manual setting] 10.7.5. Emergency operation • If you do not have the wireless remote controller (because the batteries are weak, or some other reason prevents the wireless remote controller from being used), emergency operation can be carried out at receptor unit. •...
  • Page 77: Installation And Servicing Air Conditioner Using R410A

    11 Installation and Servicing Air Conditioner Using R410A 11.1. Outline 11.1.1. About R410A refrigerant 1. Converting air conditioners to R410A Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth’s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction.
  • Page 78: Tools For Installing/Servicing Refrigerant Piping

    d. R410A refrigerating machine oil Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle.
  • Page 79: R410A Tools

    11.2.2. R410A tools 1. Copper tube gauge for clearance adjustment (used when flaring with the conventional flaring tool (clutch type)) • This gauge makes it easy to set the clearance for the copper tube to 1.0-1.5 mm from the clamp bar of the flar- ing tool.
  • Page 80 5. Charging hose • The pressure resistance of the charging hose has been raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the mani- fold ports.
  • Page 81 8. Electronic scale for refrigerant charging • Because of the high pressure and fast vaporizing speed of R410A, the refrigerant cannot be held in a liquid phase inside the charging cylinder when charging is done using the charging cylinder method, causing bubbles to form in the measurement scale glass and making it difficult to see the reading.
  • Page 82: Refrigerant Piping Work

    11.3. Refrigerant piping work 11.3.1. Piping materials It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Do not use pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog the expansion valves or capillaries.
  • Page 83 Table 11 R410A flaring dimensions Nominal Outside Wall thickness A (mm) diameter diameter (mm) R410A flaring Conventional flaring tool tool, clutch type Clutch type Wing-nut type (mm) 6.35 0 - 0.5 1.0 - 1.5 1.5 - 2.0 9.52 0 - 0.5 1.0 - 1.5 1.5 - 2.0 12.70...
  • Page 84: Installation, Transferring, Servicing

    When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to used the same nut that is used on the AC unit. b. Copper pipes Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.
  • Page 85: Transferring (Using New Refrigerant Piping)

    11.4.2. Transferring (Using new refrigerant piping) 1. Removing the unit a. Collecting the refrigerant into the outdoor unit by pumping down The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.
  • Page 86 Precaution: Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liq- uid without having to turn the cylinder around 6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor, and connect it to the connection port of the electronic scale.
  • Page 87 11.4.6. Brazing As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry nitrogen gas (N ) flow.
  • Page 88: Troubleshooting Guide

    12 Troubleshooting Guide If test operation does not proceed correctly Carry out test operation after approximately 12 hours have passed since the power was turned on (crankcase heater is energized). If operation is started by using the remote control within 1 minute of turning on the power, the outdoor unit settings will not be made correctly and correct operation will not be possible.
  • Page 89 (When remote control display shows “power supply”) Clock setting, and no timer setting (When remote control display shows “No power supply”)
  • Page 90: During Group Control Operation

    12.2. During group control operation System example 1. The main power is turned on while the transmission wires between the indoor units are not connected. (open circuit at A or B or C) Symptom Operation of indoor unit No.1 and No.3 is possible. However “check”...
  • Page 91: Test Operation And Self-Diagnosis

    12.3. Test operation and self-diagnosis 12.3.1. Test Run (Forced Cooling mode and Heating mode) 1. Always use a properly-insulated tool to operate the switch on the circuit board. (Do not use your finger or any metalic object.) 2. Never turn on the power supply unit until all installation work has been completed. 3.
  • Page 92 12.3.3. Test operation using the wired remote control 1. Check that “COOL” is displayed on the LCD, and then press the OFF/ON button to start test operation. 2. After pressing the OFF/ON button, press the TEST RUN button within 1 minute. 3.
  • Page 93 12.3.4. Self-diagnosis function The wired remote control display and the self-diagnosis LEDs (green) on the outdoor unit printed circuit board indicate where the abnormality has occured. Recalling the error display. The air conditioner No.”01” appears during normal installation and use. When using group control, a different number may appear.
  • Page 94 12.3.5. Test operation using the receiver auto button (If using wireless remote controller)
  • Page 95: Emergency Operation

    12.4. Emergency operation When using the wireless remote control and losing the remote controller, emergency operation can be operated by pressing auto button in the receiver. • Press the auto button continuously within 5 seconds If there is an abnormality in the temperature thermistor (disconnect or shorted), indoor unit cannot be operated. If abnormality detected in the indoor or outdoor unit, turn off the main power supply and find the cause.
  • Page 96: Self-Diagnosis Error Code Table

    12.5. Self-diagnosis error code table • The display screen on the wired remote control unit and the self-diagnosis LEDs (green) on the outdoor unit printed circuit board in the outdoor unit can be used to indicate where the location of a problem is. Refer to the table below to remove the cause of the problem, and then re-start the air conditioner system.
  • Page 97 Wired remote Outdoor unit printed circuit board Location or problem Check location control unit display Abnormal Detail dispaly dispaly Current detector open circuit Outdoor unit current detector fault or connec- Compressor internal protector worked Compressor fault or refrigeration system...
  • Page 98: Technical Data

    13 Technical Data 13.1. Cooling capacity performance data Ambient Temperature Air Entering Condenser (°C D.B.) Model Power Return 25°C 30°C 35°C 40°C 43°C (CS-) Source D.B. W.B. F14DB4E5 220V, 3.96 2.59 0.98 3.80 2.57 1.06 3.58 2.49 1.15 3.31 2.38 1.27 3.12 2.30...
  • Page 99 Ambient Temperature Air Entering Condenser (°C D.B.) Model Power Return 25°C 30°C 35°C 40°C 43°C (CS-) Source D.B. W.B. F18DB4E5 220V, 5.21 3.41 1.35 5.00 3.38 1.46 4.71 3.27 1.59 4.35 3.13 1.74 4.11 3.03 1.85 50Hz, 5.50 2.80 1.43 5.33 2.82 1.54...
  • Page 100: Capacity And Power Consumption

    13.2. Capacity and power consumption 13.2.1. Cooling Performance Model Cooling capacities are based on conditions CS-F14DB4E5 Single phase, 50Hz 220V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 3.8kW Outdoor temp. 35°C D.B. Standard air volume 15m /min...
  • Page 101 Model Cooling capacities are based on conditions CS-F14DB4E5 Single phase, 50Hz 230V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 3.8kW Outdoor temp. 35°C D.B. Standard air volume 15 m /min...
  • Page 102 Model Cooling capacities are based on conditions CS-F14DB4E5 Single phase, 50Hz 240V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 3.8kW Outdoor temp. 35°C D.B. Standard air volume 15 m /min...
  • Page 103 Model Cooling capacities are based on conditions CS-F18DB4E5 Single phase, 50Hz 220V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 5.0kW Outdoor temp. 35°C D.B. Standard air volume 20 m /min...
  • Page 104 Model Cooling capacities are based on conditions CS-F18DB4E5 Single phase, 50Hz 230V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 5.0kW Outdoor temp. 35°C D.B. Standard air volume 20 m /min...
  • Page 105 Model Cooling capacities are based on conditions CS-F18DB4E5 Single phase, 50Hz 240V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 5.0kW Outdoor temp. 35°C D.B. Standard air volume 20 m /min...
  • Page 106: Reaching Distance

    13.3. Reaching distance • CS-F14DB4E5 <Cooling> • CS-F18DB4E5 <Cooling>...
  • Page 107: Sound Data

    13.4. Sound data...
  • Page 108: Sound Measuring Point

    13.5. Sound measuring point 13.5.1. Indoor Unit 13.5.2. Outdoor Unit...
  • Page 109: Fan Performance

    13.6. Fan performance CS-F14DB4E5 (220/230/240V) ITEM/MODEL Indoor Unit Outdoor Unit CS-F14DB4E5 CU-J14DBE5 MODE Air Volume /min Running Current 0.15 0.12 0.60/0.61/0.62 Power Consumption 0.025 0.02 0.018 0.121/0.129/0.136 Fan Speed r/min 590/620/650 CS-F18DB4E5 (220/230/240V) ITEM/MODEL Indoor Unit Outdoor Unit CS-F18DB4E5 CU-J18DBE5...
  • Page 110: Discharge And Suction Pressure

    Fan Motor Voltage Frequency S.C. R.C. (A) IPT (kW) R.C. R.C. Current. (A) Power Con- sumption (kW) (Hz) COOL COOL (kW) (kW) COOL COOL CS-F14DB4E5 1.08 0.19 0.03 0.60 0.12 1.23 CU-J14DBE5 1.10 0.19 0.03 0.61 0.13 1.26 1.13 0.19 0.03...
  • Page 111: Exploded View (Indoor Unit)

    14 Exploded View (Indoor Unit) 14.1. CS-F14DB4E5 CS-F18DB4E5...
  • Page 112: Cs-F14Db4E5 Cs-F18Db4E5

    14.2. CS-F14DB4E5 CS-F18DB4E5...
  • Page 113: Replacement Part List (Indoor Unit)

    15 Replacement Part List (Indoor Unit) 15.1. CS-F14DB4E5 CS-F18DB4E5 REF. NO. PART NAME & DESCRIPTION QTY. CS-F14DB4E5 CS-F18DB4E5 ← BASE PAN ASS’Y CWD52K1099 ← INNER POLYSTYRENE COMPLETE CWG07C1045 ← CABINET SIDE PLATE ASS’Y CWE041112 ← CABINET SIDE PLATE ASS’Y CWE041113 ←...
  • Page 114: Exploded View (Front Grille)

    16 Exploded View (Front Grille) 16.1. CS-F14DB4E5 CS-F18DB4E5...
  • Page 115: Replacement Part List (Outdoor Unit)

    17 Replacement Part List (Outdoor Unit) Front Grille Complete (CZ-BT03P) PART DESCRIPTION PART NO. FRONT GRILLE-COMPLETE CWE11C3104 FRAME-FRONT GRILLE CO. CWE11C3101 A.S MOTOR DC, SINGLE 12V 250 OHM CWA981105J BRACKET-A.S.MOTOR CWD932391 VANE CWE241146 SHAFT CWH631038 SHAFT CWH631039 CONNECTOR-SHAFT CWH081007 BEARING CWH641008 LEAD WIRE-A.S.MOTOR CWA67C5117...
  • Page 116: Exploded View (Outdoor Unit)

    18 Exploded View (Outdoor Unit) 18.1. CU-J14DBE5 CU-J18DBE5...
  • Page 117: Cu-J14Dbe5 Cu-J18Dbe5

    18.2. CU-J14DBE5 CU-J18DBE5...
  • Page 118: Replacement Part List (Outdoor Unit)

    19 Replacement Part List (Outdoor Unit) 19.1. CU-J14DBE5 CU-J18DBE5 PART DESCRIPTION QTY. CU-J14DBE5 CU-J18DBE5 ← BASE PAN ASS’Y CWD52K1159 COMPRESSOR 5KS150DBN21 5KS205DAH21 ← ANTI-VIBRATION BUSHING CWH50055 ← NUT FOR COMP. MOUNT. CWH561049 ← GASKET FOR TERMINAL COVER CWB811017 ← CRANKCASE HEATER CWA341033 CRANKCASE HEATER CWA341035...
  • Page 119: Print Pattern

    20 Print Pattern 20.1. Indoor Unit Printed (Main)
  • Page 120: Indoor Unit Printed (Indicator)

    20.2. Indoor Unit Printed (Indicator) 20.3. Outdoor Unit (Main) [PHAAM] Printed in Malaysia SSBZ0603-00...

This manual is also suitable for:

Cu-j14dbe5Cu-j18dbe5Cs-f18db4e5

Table of Contents