Panasonic CS-F50DTE5 Service Manual
Hide thumbs Also See for CS-F50DTE5:
Table of Contents

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CS-F50DTE5

  • Page 1: Table Of Contents

    2.9. A brand-new control method 2.1. New design 2.10. Wired Remote Control 2.2. Such quietness! 2.11. Wireless Remote Control 2.3. Easy installation © 2005 Panasonic HA Air-Conditioning (M) Sdn Bhd (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.
  • Page 2 CS-F50DTE5 CU-L50DBE8 2.12. Group Control Equipment 9.12. Indoor Air Volume Up Control (DC Fan Motor Type Only) 3 Specification 3.1. Product Specification 10 Installation Instruction 4 Dimensions 10.1. Pipe length 4.1. CS-F50DTE5 10.2. Refrigerant additional charge 4.2. CU-L50DBE8 10.3. Position of the centre gravity 5 Refrigeration Cycle 10.4.
  • Page 3: Service Information

    CS-F50DTE5 CU-L50DBE8 1 Service Information Notice of Address setting for NEW Ceiling / NEW Outdoor Unit. The new Ceiling / New Outdoor models are possible to have address setting for twin control by automatic when main power supply is switched on.
  • Page 4: Operation Range

    CS-F50DTE5 CU-L50DBE8 1.4. Operation range 1.4.1. Power Supply The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage.
  • Page 5: Features

    CS-F50DTE5 CU-L50DBE8 2 Features 2.1. New design 3. Adoption of wing-shaped vanes 2.1.1. Gentle curved styling • • • • The base has gentle curves which express a functional beauty. It spreads the air quietly over a wide area. • • • • The vanes of the fan have been changed to “aerodynamic”...
  • Page 6: Easy Installation

    CS-F50DTE5 CU-L50DBE8 2.3. Easy installation 2.5. Easy maintenance 2.3.1. Easy suspension 2.5.1. Long life filter (standard equipment) • • • • A suspension bolt fixing bracket with 4-point support is attached to the main unit, which increases the space • • • • In general office environments, cleaning (maintenance) is available for installation.
  • Page 7: Low-Noise Outdoor Units

    CS-F50DTE5 CU-L50DBE8 2.7. Low-noise outdoor units [Product features] 2.7.1. Low-noise design improves in surrounding areas 1. The noise-suppressing winglet fan is a result of new research into vane design theory. The unique curved shape suppresses the generation of vortexes, thus reduces air flow noise.
  • Page 8: Improved Workability

    CS-F50DTE5 CU-L50DBE8 2.8. Improved workability 2.8.1. Pipes that are one size larger can also be connected for renewal • • • • If renewing the system, existing refrigerant pipes can be utilized so that only the indoor units need to be replaced.
  • Page 9: A Brand-New Control Method

    CS-F50DTE5 CU-L50DBE8 2.8.8. Centralized draining method • • • • Even when multiple outdoor units are installed to a wall, the drain outlets can be concentrated into a single drain pipe. This makes installation easier also improve appearance. 2.9. A brand-new control method 1.
  • Page 10: Wired Remote Control

    CS-F50DTE5 CU-L50DBE8 2.10. Wired Remote Control 1. The new design includes an easily-visible red pilot lamp. The power can be turned on and off at a single touch, without opening the cover. 2. Has a build-in thermistor, allowing indoor temperature detection in accordance with indoor conditions by switching with main unit thermistor.
  • Page 11: Group Control Equipment

    CS-F50DTE5 CU-L50DBE8 2.12. Group Control Equipment Group control by one remote [Remote side] • • • • Optional wired remote control • • • • All air conditioner units are control CZ-RD513C controlled as a whole by remote control. [Local side] •...
  • Page 12: Specification

    CS-F50DTE5 CU-L50DBE8 3 Specification 3.1. Product Specification 3.1.1. CS-F50DTE5 CU-L50DBE8 ITEM / MODEL Indoor Unit Outdoor Unit Main Body CS-F50DTE5 CU-L50DBE8 Remote CZ-RD513C (Wired) Control CZ-RL513T (Wireless) Cooling Capacity 14.0 BTU/h 47,700 Heating Capacity 16.0 BTU/h 54,600 Refrigerant Charge-less Standard Air Volume for High,...
  • Page 13: Dimensions

    CS-F50DTE5 CU-L50DBE8 4 Dimensions 4.1. CS-F50DTE5...
  • Page 14: Cu-L50Dbe8

    CS-F50DTE5 CU-L50DBE8 4.2. CU-L50DBE8...
  • Page 15: Refrigeration Cycle

    CS-F50DTE5 CU-L50DBE8 5 Refrigeration Cycle...
  • Page 16: Block Diagram

    CS-F50DTE5 CU-L50DBE8 6 Block Diagram 6.1. CS-F50DTE5...
  • Page 17: Cu-L50Dbe8

    CS-F50DTE5 CU-L50DBE8 6.2. CU-L50DBE8...
  • Page 18: Wiring Diagram

    CS-F50DTE5 CU-L50DBE8 7 Wiring Diagram 7.1. CS-F50DTE5...
  • Page 19: Cu-L50Dbe8

    CS-F50DTE5 CU-L50DBE8 7.2. CU-L50DBE8...
  • Page 20: Operation Details

    CS-F50DTE5 CU-L50DBE8 8 Operation Details 8.1. Wired Remote Control (Optional part) Name and function of each part OFF/ON button Used to start and stop the operation. FAN SPEED button Used to select the fan speed of high (HI), medium (MED), low (LO) or auto (AUTO).
  • Page 21: Wireless Remote Control (Optional Part)

    CS-F50DTE5 CU-L50DBE8 8.2. Wireless Remote Control (Optional part) Name and function of each part OFF/ON button Used to start and stop the operation. ODOUR WASH button FILTER RESET button Press to cancel the “FILTER” indicator light on the control panel.
  • Page 22: Operation Control

    CS-F50DTE5 CU-L50DBE8 9 Operation Control Description of basic control functions 9.1. Operation Mode 1. Thermostat control 2. Depend on differences between room temperature and setting temperature, Compressor running frequency will be decided and start operation. Temperature differences become same as below table, then thermostat is off.
  • Page 23 CS-F50DTE5 CU-L50DBE8 − − − − Unit using DC motor As follow the below figure, fan speed changing operation (program air). (rpm center B and is different if capacity rank is different) − − − − Unit using AC motor When 1st thermostat on condition from operation start, fan speed is hi (same as manual fan speed), after 2nd thermostat on condition, fan speed change to medium speed (same as manual medium fan speed).
  • Page 24 CS-F50DTE5 CU-L50DBE8 9.3.4. Freezing prevention control • • • • During cool or dry mode operation, if indoor evaporator temperature is going down, freezing prevention control is operated. • • • • Detail of Freezing prevention control is as follows;...
  • Page 25: Drain Pump Control

    CS-F50DTE5 CU-L50DBE8 9.3.6. Drain pump control • • • • During cooling, dry, or defrost operation, drain pump operate by following the below table. • • • • When compressor start, drain pump operation start after 10 second of indoor fan starting.
  • Page 26: Defrost Control

    CS-F50DTE5 CU-L50DBE8 Fan speed auto • • • • When operation start, or during operation, fan speed control by detecting indoor heat exchanger as follows: • • • • (K10 = Indoor heat exchanger temperature, depend on indoor type) 9.4.2.
  • Page 27 CS-F50DTE5 CU-L50DBE8 9.4.6. Heating high temperature protection • • • • During heating operation, when outdoor temperature is more than 35°C for 15 minute, compressor stop to protect compressor. • • • • After 3 minute (re-start delat control) waiting, if thermostat on condition, outdoor unit re-start.
  • Page 28: Louver Control

    CS-F50DTE5 CU-L50DBE8 9.5. Louver Control 9.5.1. Louver control for cassette type • • • • When power is on, at the same time, louver start initializing toward to close Direction. • • • • During operation, stopping, thermostat off condition, louver angle set manual or auto depend on remote controller setting.
  • Page 29 CS-F50DTE5 CU-L50DBE8 9.5.2. Ceiling type louver control • • • • When power is on, at the same time, louver initialize 2 times. • • • • During operation, stopping, thermostat is off condition, louver angle change as below table by manual setting or auto setting of remote controller.
  • Page 30: Odour Removing Operation

    CS-F50DTE5 CU-L50DBE8 9.6. Odour Removing Operation • • • • During stop condition, or cooling operation, when pushing the [ODOUR] button for 5 second, operation change to the odour removing operation. • • • • Operation detail is as follows;...
  • Page 31: Energy Save Operation

    CS-F50DTE5 CU-L50DBE8 9.7. Energy Save Operation • • • • During cooling operation, or heating operation, when pushing the [ECONOMY] button in the wired remote controller, energy save operation start and [ECO] sign is displayed at LCD display panel of wired remote controller ([ECONOMY] sign is displayed at LCD display panel of wireless remote controller).
  • Page 32: Pump Down Operation

    CS-F50DTE5 CU-L50DBE8 9.11. Pump Down Operation • • • • When pushing the [PUMP DOWN] button on the outdoor PCB for 1 second, pump down operation start. Detail of pump down operation is shown at below table. • • • • During pump down operation, push the [PUMP DOWN] button once again for 1 second, pump down operation stop.
  • Page 33: Installation Instruction

    CS-F50DTE5 CU-L50DBE8 10 Installation Instruction 10.1. Pipe length • • • • CORRECTION OF COOLING CAPACITY AND HEATING CAPACITIES 1. Correction of cooling and heating capacities according to the connecting pipe length. The Data of cooling capacities (marked on the name plate) are based on 5 meters connecting pipe and horizontal installation.
  • Page 34: Refrigerant Additional Charge

    CS-F50DTE5 CU-L50DBE8 10.2. Refrigerant additional charge 1. Piping installation by standard piping • • • • At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30 m. (Refer the following table) But when the piping length exceeds 30m, additional charge is required according to the following table.
  • Page 35: Indoor Unit Installation

    CS-F50DTE5 CU-L50DBE8 10.4. Indoor unit installation CEILING TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS Precautions in terms of safety Carry out installation work with reliability after throughout reading of this “Precautions in terms of safety”. • • • • Precautions shown here are differentiated between Warnings Cautions .
  • Page 36 CS-F50DTE5 CU-L50DBE8 Cautions Carry out Earthing work. Drain piping should be made to ensure secure drainage Do not connect the Earth return to the gas pipe, according to the manual for installation work and carry out the water line pipe, lightning rod and telephone lines.
  • Page 37: Installation Of Indoor Unit

    CS-F50DTE5 CU-L50DBE8 • • • • Make sure the ventilation fan for smoke-collection hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • • • • Make enough distance from cooking room to install the air conditioner in such place where it may not suck in oily steam.
  • Page 38 CS-F50DTE5 CU-L50DBE8 Fastening the hanging bracket * Use either W3/8 or M10 bolts and nuts (local supplied) • • • • Fastening the hanging bracket Warning Be sure to tighten the nut and bolt to prevent the unit from falling.
  • Page 39 CS-F50DTE5 CU-L50DBE8 10.4.4. Refrigerant piping Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit.(Additional charging, etc.) 1. Brazing for piping. a. Execute brazing before tightening the flare nut. b. Brazing must be executed while blowing nitrogen gas.
  • Page 40 CS-F50DTE5 CU-L50DBE8 In the case of left piping Be sure to perform heat insulation on the drain piping. Caution If insulation is insufficient, dew may form. 1. Remove both the internal and external plugs. This causes water leakage. 2. Use a wrench or pliers to remove the plugs.
  • Page 41 CS-F50DTE5 CU-L50DBE8 10.4.7. Electrical wiring As to the main power source and cable size of outdoor unit, read the installation manual attached to the outdoor unit. The units must be connected to the supply cables for fixed wiring by qualified technician.
  • Page 42 CS-F50DTE5 CU-L50DBE8 10.4.8. Settings Do not operate the remote controller within 1 minute after turning on the power of the indoor unit. When using group control with the standard type, at least 1 unit must be set at No.1 at the indoor unit.
  • Page 43: Hand Over

    CS-F50DTE5 CU-L50DBE8 • • • • First, press the OFF/ON ( ) button. • • • • Then press the TEST RUN button within 1 minute of pressing the OFF/ON ( ) button. • • • • Next, select the operation modes.
  • Page 44: Outdoor Unit Installation

    CS-F50DTE5 CU-L50DBE8 10.5. Outdoor unit installation AIR CONDITIONERS OUTDOOR UNIT INSTALLATION INSTRUCTIONS Precautions in terms of safety Carry out installation work with reliability after thorough reading of this “Precautions in terms of safety”. • • • • Precautions shown here are differentiated between Warnings Cautions .
  • Page 45 CS-F50DTE5 CU-L50DBE8 Warnings Wiring shall be connected securely using specified cables and fix them securely so that external force of the cables may not transfer to the terminal connection section. Imperfect connection and fixing leads to fire, etc. Cautions Carry out Earthing work.
  • Page 46 CS-F50DTE5 CU-L50DBE8 b. Prevention measure for refrigerant piping Prevention measure for refrigerant piping is very important work to prevent water-dust-rubbish from getting in. All piping terminals needs sealing such as shown below. Place Period of work Method of seal Outside...
  • Page 47 CS-F50DTE5 CU-L50DBE8 For the use of a gas cylinder without siphon inside, turn it upside down and use it. (We recommend manifold with sight glass.) Caution Do not use a “CHARGE CYLINDER”. Caution As a rule, please collect all existing refrigerants in the system outside the system when the refrigerant leakage occurs by the system.
  • Page 48 CS-F50DTE5 CU-L50DBE8 12. Be sure to leave enough space around the outdoor unit to maintain proper performance and to allow access for routine maintenance. • • • • Allow enough space from any obstacles as shown in Fig. 1.2 below in order to prevent short-circuits from occurring.
  • Page 49 CS-F50DTE5 CU-L50DBE8 • • • • If a drain pipe needs to be installed, insert the accessory drain elbow into the mounting hole at the bottom of the outdoor unit, and connect a hose with an inside diameter of 15mm to this drain elbow.
  • Page 50: Charging With Refrigerant

    CS-F50DTE5 CU-L50DBE8 3. Notes when connecting the refrigerant pipes. • • • • Use clean copper, pipes with no water or dust on the insides. • • • • Use phosphorus-free, unjointed copper pipes for the refrigerant pipes. • • • • If it is necessary to cut the refrigerant pipes, be sure to use a pipe cutter, and use compressed nitrogen or an air blower to clean out any foreign particles from inside the pipe.
  • Page 51 CS-F50DTE5 CU-L50DBE8 • • • • Pump down operation − − − − Operate the pump down according to the following procedures. Procedure Notes 1. Confirm the valve on the liquid side and the gas side is surely open. 2. Press the PUMP DOWN switch on outdoor printed board for 1 Perform the cooling operation for five minutes or more.
  • Page 52 CS-F50DTE5 CU-L50DBE8 Earth lead wire shall be longer than other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage. • • • • Power supply specifications...
  • Page 53 CS-F50DTE5 CU-L50DBE8 10.5.10. Connecting power supply cables CAUTION • • • • For three phase model, never operate the unit by pressing the electromagnetic switch. • • • • Never correct the phase by switching over any of the wires inside the unit.
  • Page 54 CS-F50DTE5 CU-L50DBE8 NOTE If the self-diagnosis function reports a problem but more than one problem has developed at the indoor and/or outdoor units, the problem display on the remote control unit may not match the LED display on the outdoor unit printed circuit board. In such cases, check both locations and remove the causes of the problems.
  • Page 55: Wired Remote Control Installation

    CS-F50DTE5 CU-L50DBE8 10.6. Wired remote control installation Wired Remote Control Installation Manual • • • • Before installing the wired remote controller, be sure to thoroughly read the “Notes with regard to safety” section of the installation manual provided with the indoor unit.
  • Page 56 CS-F50DTE5 CU-L50DBE8 If no displays appear on the remote controller, check while referring to “If no remote controller displays appear” in “5 Test operation”. • • • • The remote control cable is live during use, so please be careful with it.
  • Page 57 CS-F50DTE5 CU-L50DBE8 • • • • Strip the end of the remote control cable which is to be connected to the remote controller. (Refer to the illustration below) • • • • Route the remote control cable inside the lower case in accordance with the intended feeding- out direction. (Refer to the illustration below.)
  • Page 58 CS-F50DTE5 CU-L50DBE8 If remote control cable is embedded If installing with the remote control cable exposed 1. Embed an outlet box (JIS C 8336) into the wall, and then secure 1. Secure the remote controller base plate to the wall with two the remote controller base plate to the outlet box with the two accessory 4 mm screws.
  • Page 59 CS-F50DTE5 CU-L50DBE8 Automatic address resetting for group control • • • • The address settings for group control (air conditioner Nos. 1 to 16) can be reset automatically. 1. When operation is stopped, press for 5 seconds, continue the TEST RUN switch to display “00” (will be LOCAL MODE).
  • Page 60: Test Operation

    CS-F50DTE5 CU-L50DBE8 10.6.5. Test operation • • • • Turn on the main power. • • • • After 3 minutes have passed since the power was turned on, press the OFF/ON switch on the remote controller. (No operation occurs within 3 minutes after the power was turned on.)
  • Page 61 CS-F50DTE5 CU-L50DBE8 • • • • You can then switch between the display for the previous problem and the problem before that by pressing the UP (TIMER) DOWN (TIMER) switches. • • • • Press the CHECK switch once more to return to the normal display.
  • Page 62: Wireless Remote Control Installation Manual

    CS-F50DTE5 CU-L50DBE8 10.7. Wireless remote control installation manual Wireless Remote Control Installation Manual • • • • Before installing the wireless remote controller, be sure to thoroughly read the “Notes with regard to safety” section of the installation manual provided with the indoor unit.
  • Page 63 Attach the receptor unit onto the decorative panel of the indoor unit as shown in the figure below. 1. Remove the “corner cover” at the decorative panel indicate “Panasonic” logo left side. 2. Attach the receptor unit which same position.
  • Page 64 CS-F50DTE5 CU-L50DBE8 1. Route the joint cord for wiring as shown in the figure (figure of the back of decorative panel) below. Pass the cord through the hook of the decorative panel, taking care that the cord does not run on the heat insulator, etc.
  • Page 65 CS-F50DTE5 CU-L50DBE8 Receptor unit (for ceiling type) assembly procedure Attach the receptor unit onto the indoor main unit as shown in the figure below. Remove the air-intake grille and the side cover. To remove the side cover, remove the fixing screw each on the left and the right and pull the side cover towards you.
  • Page 66 CS-F50DTE5 CU-L50DBE8 10.7.4. Address setting for wireless remote controller and receptor unit (only when using more than one indoor unit) • • • • Only the air conditioner units which receptor unit address numbers match the remote controller address number can be operated.
  • Page 67 CS-F50DTE5 CU-L50DBE8 NOTE • • • • If the batteries are replaced or the remote controller is reset, the address setting will return to ADDRESS1, so you will need to repeat the address setting again. All setting details which are stored in memory will be cleared, so you will need to repeat the setting.
  • Page 68: Emergency Operation

    CS-F50DTE5 CU-L50DBE8 [Manual setting] 10.7.5. Emergency operation • • • • If you do not have the wireless remote controller (because the batteries are weak, or some other reason prevents the wireless remote controller from being used), emergency operation can be carried out at receptor unit.
  • Page 69: Twin

    CS-F50DTE5 CU-L50DBE8 10.8. Twin 10.8.1. Twin Operation • • • • Simultaneous air conditioning of wide spaces and corners is possible. Indoor units with same horsepowers can even be used in combination. • • • • Master unit and slave-units can be set automatically in twin systems. No address setting is necessary.
  • Page 70: Installation And Servicing Air Conditioner Using R410A

    CS-F50DTE5 CU-L50DBE8 11 Installation and Servicing Air Conditioner Using R410A 11.1. Outline 11.1.1. About R410A refrigerant 1. Converting air conditioners to R410A Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth’s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction.
  • Page 71: Tools For Installing/Servicing Refrigerant Piping

    CS-F50DTE5 CU-L50DBE8 d. R410A refrigerating machine oil Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle.
  • Page 72: R410A Tools

    CS-F50DTE5 CU-L50DBE8 11.2.2. R410A tools 1. Copper tube gauge for clearance adjustment (used when flaring with the conventional flaring tool (clutch type)) • • • • This gauge makes it easy to set the clearance for the copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool.
  • Page 73 CS-F50DTE5 CU-L50DBE8 5. Charging hose • • • • The pressure resistance of the charging hose has been raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports.
  • Page 74 CS-F50DTE5 CU-L50DBE8 8. Electronic scale for refrigerant charging • • • • Because of the high pressure and fast vaporizing speed of R410A, the refrigerant cannot be held in a liquid phase inside the charging cylinder when charging is done using the charging cylinder method, causing bubbles to form in the measurement scale glass and making it difficult to see the reading.
  • Page 75: Refrigerant Piping Work

    CS-F50DTE5 CU-L50DBE8 11.3. Refrigerant piping work 11.3.1. Piping materials It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Do not use pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog the expansion valves or capillaries.
  • Page 76 CS-F50DTE5 CU-L50DBE8 Table 11 R410A flaring dimensions Nominal Outside Wall thickness A (mm) diameter diameter (mm) R410A flaring Conventional flaring tool (mm) tool, clutch type Clutch type Wing-nut type 6.35 0 - 0.5 1.0 - 1.5 1.5 - 2.0 9.52 0 - 0.5...
  • Page 77: Installation, Transferring, Servicing

    CS-F50DTE5 CU-L50DBE8 b. Copper pipes Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.
  • Page 78 CS-F50DTE5 CU-L50DBE8 11.4.2. Transferring (Using new refrigerant piping) 1. Removing the unit a. Collecting the refrigerant into the outdoor unit by pumping down The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.
  • Page 79 CS-F50DTE5 CU-L50DBE8 3. Fully open the handle Lo of the manifold gauge, turn on the power of the vacuum pump and continue the vacuum process for at least one hour. 4. Confirm that the low pressure gauge shows a reading of -0.1 Mpa (-76 cmHg), then fully close the handle Lo, and turn off the vacuum pump.
  • Page 80 CS-F50DTE5 CU-L50DBE8 11.4.6. Brazing As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry nitrogen gas (N ) flow.
  • Page 81: Troubleshooting Guide

    CS-F50DTE5 CU-L50DBE8 12 Troubleshooting Guide 12.1. Self-diagnosis error code table • • • • The display screen on the wired remote control unit and the self-diagnosis LEDs (green) on the outdoor unit printed circuit board in the outdoor unit can be used to indicate where the location of a problem is.
  • Page 82 CS-F50DTE5 CU-L50DBE8 Wired remote Outdoor unit printed circuit board LED Location or problem Check location control unit display Abnormal Detail 302 303 304 305 306 307 308 309 dispaly dispaly Outlet temperature sensor Outlet temperature sensor lead wire, problem connector CN-TH1 Compressor suction Suction temperature sensor (SUC T.
  • Page 83: Replacement Parts

    CS-F50DTE5 CU-L50DBE8 13 Replacement Parts 13.1. Indoor unit...
  • Page 84 CS-F50DTE5 CU-L50DBE8...
  • Page 85 CS-F50DTE5 CU-L50DBE8...
  • Page 86 CS-F50DTE5 CU-L50DBE8 PART DESCRIPTION QTY. CS-F50DTE5 CABINET TOP PLATE CWE001016 CABINET FRONT PLATE CWG07K1008 CABINET SIDE PLATE (L) CWD63K1003 VANE SUPPORTER (L) CWG071144 CATCHER CWH601005 CABINET SIDE PLATE (R) CWD63K1004 VANE SUPPORTER (R) CWG071145 BLOWER WHEEL BASE ASS’Y CWD90K1008 BRACKET FAN MOTOR ASS’Y...
  • Page 87 CS-F50DTE5 CU-L50DBE8 INSTALLATION INSTRUCTION CWF612642 All parts are supplied from PHAAM, Malaysia (Vendor Code: 061)
  • Page 88: Outdoor Unit

    CS-F50DTE5 CU-L50DBE8 13.2. Outdoor unit...
  • Page 89 CS-F50DTE5 CU-L50DBE8...
  • Page 90 CS-F50DTE5 CU-L50DBE8...
  • Page 91 CS-F50DTE5 CU-L50DBE8 PART DESCRIPTION QTY. CU-L50DBE8 BASE PAN ASS’Y CWD52K1110 COMPRESSOR 5JD420XBA22 ANTI-VIBRATION BUSHING CWH50055 NUT FOR COMP. MOUNT. CWH4582065 PACKING CWB811017 CRANKCASE HEATER CWA341013 CONDENSER COMPLETE CWB32C1594 TUBE ASS’Y(PRESSURE SWITCH) CWT023392 DISCHARGE MUFFLER CWB121014 HIGH PRESSURE SWITCH CWA101007 3-WAYS VALVE (GAS)
  • Page 92: Electronic Circuit Diagram

    CS-F50DTE5 CU-L50DBE8 14 Electronic Circuit Diagram 14.1. Indoor unit SCHEMATIC DIAGRAM 1/4 TO CN-OPT2 CN-TIMER 20k 1% 10.0k 1% 10.0k 1% 10.0k 1% 10.0k 1% 0.047 25V 0.047 25V 8 7 6 5 8 7 6 5 0.047 25V 0.047 25V...
  • Page 93 CS-F50DTE5 CU-L50DBE8 SCHEMATIC DIAGRAM 2/4 TO CN-OPT3 TO CN-DISP R108 R138 0.01 6.3V R107 R131 R106 0.01 R130 3300p 5.1k R123 R118 2SC3052F R115 R116 R117 5.6k 1000p 1/4W 1/4W TLP421 R148 (BL) LED1 6.3V VSS3 VDD2 VSS2 VREF+ A52101C62PD...
  • Page 94 CS-F50DTE5 CU-L50DBE8 SCHEMATIC DIAGRAM 3/4 2SC18741 (FA) RD16UJ (N3) RY-CON GGE-134P SY-110AV IA5-E 1.15k 1% 1/4W 600V 1A RD6.2E R110 275VAC R111 ZD10 NONE RD6.2E 2SC3052F TLP421 R113 (BL) R112 RD4.7UJ TLP421 R114 1000p 4.7k b 10k 250VAC 4.7k R151 2SC1841 1.8k...
  • Page 95 CS-F50DTE5 CU-L50DBE8 SCHEMATIC DIAGRAM 4/4 ELECTRONIC CONTROL UNIT CN-PWR 3 4 2 1 3 4 2 1 SW301 SW302 SW303 CN-LYN LND2 DC782 CN-DRV DNDN DC782 FROM CN-OPT2 CN-FM (VH9-5) SW201 FAN MOTOR IC201 C-FV1 (RED) 3 GND C-FV2 2 Vcc...
  • Page 96: Outdoor Unit

    CS-F50DTE5 CU-L50DBE8 14.2. Outdoor unit ** Electronic Circuit Diagram *** CU-L50DBE8 SCHEMATIC DIAGRAM 1/5 ELECTRONIC CONTROL UNIT RY-V1 CN-V1 GAS-BYPASS VALVE CN-V2 RY-V2 LIQUID-BYPASS VALVE RY-V1 RY-V2 CN-HOT RY-HOT 4 WAY VALVE (VH3-2) (BLUE) SSR1 ZNR2 ULM2003ADR (VH3-2) SSR2 µ...
  • Page 97 CS-F50DTE5 CU-L50DBE8 SCHEMATIC DIAGRAM 2/5 CN-CPU R256 R253 R255 R254 ULM2003ADR µ ULM20 µ P42/TM9A1 ADIN00 ADIN01 ADIN10 P83/ADIN11 MN103S52GPL 0.1µ R271 P87/ADIN23 P90/ADIN24 ADIN25 ADIN26 R106 R182 µ µ 0.047 µ R159 R121 10 MHz R114 (15px2) µ 12.1K 0.047...
  • Page 98 CS-F50DTE5 CU-L50DBE8 SCHEMATIC DIAGRAM 3/5 (NOICE FILTER) OF SCHEMATIC DIAGRAM 5 L1-OUT(BLU) L2-OUT(YLW) L3-OUT(BLK) MAGNET RELAY CN-RY1 TO (CN-001) SCHEMATIC DIAGRAM 4 MAGNET RELAY CN-RY2 RY-PWR2 R105 ULM2003ADR C129 450V 56 µ ETS29AK7W1AC EG01Z 11 1 AM01Z 0.22 µ µ...
  • Page 99 CS-F50DTE5 CU-L50DBE8 SCHEMATIC DIAGRAM 4/5 REACTOR DCP OUT R400 C400 C401 C402 R401 µ µ µ 400v 400v 400v DIODE ZNR400 BRIDGE C403 C404 C405 µ µ µ R403 400v 400v 400v DCN OUT 1.24K R200 RD28ER C101 C102 µ...
  • Page 100 CS-F50DTE5 CU-L50DBE8 SCHEMATIC DIAGRAM 5/5 TO MAGNETIC RELAY IN SCHEMATIC DIAGRAM 3 L1-OUT L1-IN L2-IN L3-OUT L3-IN N-IN FUSE T6.3A 250V CN-001 TO (CN-AC) SCHEMATIC DIAGRAM 3 ZNR204 INDOOR UNIT ZNR205 CT200 JP201 TO (CN-COM) IN SCHEMATIC DIAGRAM 1 590 589 591 599 400 501...
  • Page 101: Wired Remote Control

    CS-F50DTE5 CU-L50DBE8 14.3. Wired remote control...
  • Page 102: Wireless Remote Control

    CS-F50DTE5 CU-L50DBE8 14.4. Wireless remote control...
  • Page 103: Print Pattern

    CS-F50DTE5 CU-L50DBE8 14.5. Print pattern 14.5.1. Indoor unit • • • • INDOOR UNIT PRINTED CIRCUIT BOARD (MAIN)
  • Page 104 CS-F50DTE5 CU-L50DBE8 • • • • INDOOR UNIT PRINTED CIRCUIT BOARD (INDICATOR)
  • Page 105 CS-F50DTE5 CU-L50DBE8 14.5.2. Outdoor unit • • • • OUTDOOR UNIT PRINTED CIRCUIT BOARD (MAIN)
  • Page 106 CS-F50DTE5 CU-L50DBE8 • • • • OUTDOOR UNIT PRINTED CIRCUIT BOARD (POWER) • • • • OUTDOOR UNIT PRINTED CIRCUIT BOARD (SERVICE) [PHAAM] Printed in Malaysia...

This manual is also suitable for:

Cu-l50dbe8

Table of Contents