Installation; Connecting The Modem; Figure 1: 5902 Module Layout - Bell 5902 Hardware Manual

Table of Contents

Advertisement

4

Installation

The installation of the 5902 modem requires mounting the modem on the 7.5mm by 35mm DIN rail
and connecting the 5902 modem to the system I/O Bus. Refer to the System Configuration Guide,
at the beginning of this manual, for complete information on system layout, I/O Bus cable routing
and 5902 modem installation.
4.1

Connecting the Modem

The 5902 modem is normally connected to the SCADAPack I/O Bus through the I/O Bus
Connectors as shown in figure 1.In this configuration the SCADAPack provides a modem reset
(/RST) signal and a signal to enable the leds (LEDON) on the 5902 modem.
The 5902 modem is also available in a stand alone (SA) configuration. In this configuration the
5902 is not connected to a SCADAPack controller and the modem reset (/RST) signal and a signal
to enable the leds (LEDON) on the 5902 modem are not available. Two jumpers, J1 and J2, are
included to enable these signals on the 5902SA modem. Figure 1: 5902 Module Layout shows the
location of the jumpers.
5902 Modem
Remove jumper at J1 (/RST).
Remove jumper at J2 (LEDON).
5902SA Modem
Install jumper at J1 (/RST).
Install jumper at J2 (LEDON).
Connector
LEDON Jumper (J2)
TX Gain Jumper (J3)
/RST Jumper (J1)
RJ-45 Jack
5902 Bell 202 Modem Hardware Manual
October 19, 2007
I/O Bus
Configuration
Switches
TX Gain
Adjustment
+
+
+
Tx/Rx
Rx
KEY

Figure 1: 5902 Module Layout

Status LEDs
I/O Bus
Connector
RX Gain
Adjustment
Termination
Block
RS-232 DCE
Connector
+
RCD
9