Figure 5: Example 4 - Passcode Worksheet; Table 6: Menu/Function List Description; Menu Item And Function - Bosch D1256 Installation Instructions Manual

Fire command center/fire alarm annunciators
Table of Contents

Advertisement

D1256/D1257
Installation

4.3.4.1 Menu Item and Function

Bosch Security Systems recommends programming the first ten menu items as indicated in Table 6. The first four menu
items must be programmed as indicated in Table 6 for the D1256 to function properly. The first four keys on the D1256
annunciator execute the first four menu items turned on at the command center address. Menu items five through ten
are optional features that can be programmed into the D1256 system.
See the Fire System User's Guide (P/N: 71-06991-000) for further explanation of these optional programmable items.
Note:
Please make sure that CF 128 to 131 and any other functions that you are using in the menu are programmed
E (Enabled) not P (Passcode Required).
4.3.4.2 CC Address #
Program command center addresses to YES for the first four menu items and the optionally program menu items five
through ten as YES.
4.3.5
Passcode Worksheet
Passcode Worksheet
User
User
Flag
Passcode
000
00
_ _ _ _ _ _
001
01
1 2 5 6 0 0
4.3.5.1 Passcode
A special passcode must be programmed as a valid passcode for the system to work. This passcode is used in Custom
Functions 128 and 131. Any user number can be used to establish this mandatory valid passcode. It must additionally be
created as a valid passcode in the area to which the D1256 is assigned. Bosch Security Systems recommends using
authority level 14 in conjunction with the passcode you choose (see Authority Level Selections).
74-06925-000-H
Menu Item
Function
1
128
2
129
3
130
4
131
5
9
6
10
7
12
8
21
9
29
10
32

Table 6: Menu/Function List Description

User
Window
1
2
4
_ _
15
15
15
_ _
14
__
__
Figure 5: Example 4 – Passcode Worksheet
D1256/D1257 Installation Instructions
Description
ALARM SILENCE?
TROUBLE SILENCE?
DETECTOR RESET?
ANUNCIATOR RESET
VIEW MEMORY?
VIEW PT STATUS?
FIRE TEST?
VIEW LOG?
REMOTE PROGRAM?
DISPLAY REV?
Area Auth
5
6
7
8
User Name
15
15
15
15
__________________________________
__
__
__
__
__________________________________