Toshiba RAS-M10NKV-E Service Manual page 38

Split type air conditioner
Hide thumbs Also See for RAS-M10NKV-E:
Table of Contents

Advertisement

Block distinction
Check
Check
Block
code
code
Outdoor P.C.
board
Not
displayed
Outdoor P.C.
board
Others
(including
compressor)
Operation of diagnosis function
Cause of operation
conditioner
status
Inverter over-current
All off
protective circuit operates.
(Short time)
Position-detect circuit
All off
error or short-circuit
between windings of
compressor
Current-detect circuit
All off
error
Being out of place,
All off
disconnection or short-
circuit of outdoor temp.
sensor
Disconnection or short-
All off
circuit of discharge temp.
sensor
Outdoor fan drive system
All off
error
Outdoor temp. sensor
Operation
error
continues.
Compressor drive output
All off
error, Compressor error
(lock, missing, etc.),
Break down
Error exclusive for
All off
multiple type
Compressor does not
All off
rotate. (Current protective
circuit does not operate
when a specified time
passed after compressor
had been activated.)
Discharge temp. ex-
All off
ceeded 120°C.
Break down of
All off
compressor
– 37 –
Air
Remarkes
Displayed when
Even if trying operation again, all
error is detected.
operations stop immediately. : Replace
P .C. board.
Displayed when
1. Even if connecting lead wire of
error is detected.
compressor is removed, position-
detect circuit error occurred. :
Replace P.C. board.
2. Measure resistance between wires of
compressor, and perform short-
circuit. : Replace compressor.
Displayed when
Even if trying operation again, all
error is detected.
operations stop immediately. : Replace
P .C. board.
Displayed when
Check 5-serial LED.
error is detected.
1. Check P.C. board.
Displayed when
1. Check discharge temp. sensor (TD).
error is detected.
2. Check P.C. board.
Displayed when
Position-detect error, over-current
error is detected.
protective operation of outdoor fan drive
system, fan lock, etc. : Replace P.C.
board or fan motor.
1. Check outdoor temp. sensor (TO).
——
2. Check P.C. board.
Displayed when
Check 5-serial LED.
error is detected.
When 20 seconds passed after start-up,
position-detect circuit error occurred. :
Replace compressor.
Displayed when
Check 5-serial LED.
error is detected.
1. Miswiring of connecting wire of A/B/
C/D rooms in indoor/outdoor units
2. Check gas leakage.
3. Check disconnection of sensor.
4. Electronic control valve error
Displayed when
1. Trouble on compressor
2. Trouble on wiring of compressor
error is detected.
(Missed phase)
1. Check dischage temp. sensor (TD).
Displayed when
error is detected.
2. Degassing
3. Trouble on P.M.V.
1. Check power voltage.
Displayed when
error is detected.
(220–240 V ±10%)
2. Overload operation of refrigeration
cycle
Check installation condition
(Short-circuit of outdoor diffuser).
FILE NO. SVM-05019
Judgment and action