Laars MAGNATHERM MGH2000 Installation And Operation Instructions For page 75

Modulating boiler water heater
Table of Contents

Advertisement

MagnaTherm Boilers and Water Heaters
code
Description
26
internal fault:
Static flame ripple
27
internal fault:
Flame rod shorted to ground detected
28
internal fault:
A/D linearity test fails
29
internal fault:
Flame bias cannot be set in range
30
internal fault:
Flame bias shorted to adjacent pin
31
internal fault:
SLO electronics unknown error
32-46 internal fault:
Safety Key 0 through 14
47
Flame Rod to ground leakage
48
Static flame (not flickering)
49
24 VAc voltage low/high
50
Modulation fault
51
Pump fault
52
Motor tachometer fault
Lockout
Procedure
or Hold
H
internal fault
1. Reset module
2. if fault repeats, replace module.
H
internal fault
1. Reset module
2. if fault repeats, replace module.
H
internal fault
1. Reset module
2. if fault repeats, replace module.
H
internal fault
1. Reset module
2. if fault repeats, replace module.
H
internal fault
1. Reset module
2. if fault repeats, replace module.
H
internal fault
1. Reset module
2. if fault repeats, replace module.
L
internal fault
1. Reset module
2. if fault repeats, replace module.
H
internal fault
1. Reset module
2. if fault repeats, replace module.
H
internal fault
1. Reset module
2. if fault repeats, replace module.
H
1. check the module and display connections.
2. check the module power supply and make
sure that frequency, voltage and VA meet the
specifications.
H
internal sub-system fault.
1. Review alert messages for possible trends.
2. correct possible problems.
H
internal sub-system fault.
1. Review alert messages for possible trends.
2. correct possible problems.
H
internal sub-system fault.
1. Review alert messages for possible trends.
2. correct possible problems.