Laars MAGNATHERM MGH2000 Installation And Operation Instructions For page 28

Modulating boiler water heater
Table of Contents

Advertisement

Page 24
Space heating zone circuit
Air vent
Water feed
controls
Expansion tank
4 pipe dia. max.
Note -
This drawing is a schematic
representation of a piping style,
and is not intended to be used
as a working installation drawing.
Local code requirements
must be met.
figure 10. Hydronic Piping — multiple Boilers, Indirect DHW off of one Boiler
Space heating zone circuits
4 pipe dia. max.
Common piping must be sized for the
combined water ow of all the boilers.
High temp. space heating zone circuit
4 pipe dia. max.
note: Boiler side of the indirect tank
must be sized to accept the
BTU load of the boiler.
LAARS Heating Systems
Note -
Indirect pump
must be sized
for boiler and
indirect
Indirect
DHW tank
Note -
In this piping arrangement,
the boiler pump must turn o
during DHW operation.
Anti-scald
mixing valve
Domestic
hot water
out
Cold
water