Character
Enter the maximum delay (in msec) between received serial characters before
Timeout
packet is sent via network.
Packet Size
The number of received bytes that will be buffered before a packet is sent via
the network.
Multicast Group
Enter the UDP port number that all members of the group will use (i.e. all group
Port
members should use the same port number).
Multicast Group
Enter a valid Multicast IP Address identifying the group (i.e. all group members
IP Address
should use the same Multicast Group IP Address). Valid Multicast IP
Addresses are in the range 224.0.1.0 to 238.255.255.255.
Modbus - Allows a serial Modbus Client (Master) to connect with a single
Serial Gateway
Mode
Ethernet Modbus TCP Server (Slave)
Character
Enter the maximum delay (in msec) between received serial characters before
Timeout
packet is sent via network.
Packet Size
The number of received bytes that will be buffered before a packet is sent via
the network.
Enter the TCP port number of the remote server (i.e. the remote port to
Modbus Server
Port
automatically connect to).
Modbus Server IP
Enter the IP Address of the remote server (i.e. the remote IP Address to
automatically connect to).
Address
RS-232 / RS485 Modbus TCP/RTU Converter
Modbus Server
Port number used for the Modbus TCP – Standard port is 502.
TCP Port
Pauses Between
Enter the delay between serial request retries in milliseconds
Requests
Response
Enter the serial response timeout in milliseconds – a serial retry will be sent if a
Timeout
response is not received within this timeout.
Connection
Enter the TCP connection timeout in seconds – if no Modbus/TCP data is
Timeout
received within this timeout then the TCP connection will be dropped. Set this
field to zero for no timeout.
Maximum
Enter the maximum number of request retries performed serially.
Request Retries
Maximum
Enter the maximum number of simultaneous TCP connections to the server
Connections
allowed.