Unitary products group PT9-UP Installation Manual

Unitary products group PT9-UP Installation Manual

High efficiency tubular heat exchanger series (two stage upflow) 40 - 120 mbh input (11.7 - 35.1 kw) input
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: PT9-UP / FC9T-UP / FL9T-UP
(Two Stage Upflow)
40 - 120 MBH INPUT
(11.7 - 35.1 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Thermostat Chart - AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat Chart - HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Twinning Wiring Diagram - 1H/1C Thermostat . . . . . . . . . . . . . . . . . 13
Twinning Wiring Diagram - 2H/1C Thermostat . . . . . . . . . . . . . . . . . 13
Twinning Wiring Diagram - 2H/2C Thermostat . . . . . . . . . . . . . . . . . 13
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Termination Configuration - 1 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 5
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Recommended Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . . . 8
Nominal Manifold Pressure - Low Fire . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical and Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Maximum Equivalent Pipe Length . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Equivalent Length of Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Elbow Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . . . . . . . . . . . .13
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .21
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
LIST OF FIGURES
Termination Configuration - 2 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Termination Configuration - 2 Pipe Basement . . . . . . . . . . . . . . . . . .17
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .19
Condensate Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Pressure Switch Tube Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
LIST OF TABLES
(All Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . .19
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Blower Performance CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Field Installed Accessories - Non Electrical . . . . . . . . . . . . . . . . . . . .28
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
272313-UIM-A-0407

Advertisement

Table of Contents
loading

Summary of Contents for Unitary products group PT9-UP

  • Page 1: Table Of Contents

    INSTALLATION MANUAL HIGH EFFICIENCY EFFICIENCY RATING TUBULAR HEAT EXCHANGER SERIES CERTIFIED MODELS: PT9-UP / FC9T-UP / FL9T-UP (Two Stage Upflow) ISO 9001 Certified Quality 40 - 120 MBH INPUT Management System (11.7 - 35.1 KW) INPUT LIST OF SECTIONS SAFETY ..........1 COMBUSTION AIR AND VENT SYSTEM .
  • Page 2: Safety

    • Refer to the unit rating plate for the furnace model number, and then see the dimensions page of this instruction for return air ple- num dimensions in Figure 1. The plenum must be installed according to the instructions. Unitary Products Group...
  • Page 3 248 CMR 5.08(2)(a)1 through 4. than 18 inches (46 cm) above the floor, and the furnace must be located or protected to avoid physical damage by vehicles. Unitary Products Group...
  • Page 4: Ductwork

    In this example, the duct system attached to the plenum has a sufficient area so that the furnace operates at the specified external static pres- sure and within the air temperature rise specified on the nameplate. Providing the return duct is properly sized as well. Unitary Products Group...
  • Page 5: Minimum Duct Sizing For Proper Airflow

    This access cover ing, Refer to the ASHRAE Fundamentals Handbook, Chapter on shall be attached in such a manner as to prevent leaks. “DUCT DESIGN” or a company that specializes in Residential and Mod- ular Home duct designs. Unitary Products Group...
  • Page 6: Filters

    The furnace base is equipped with a rectangular blockoff panel that can All applications require the use of a filter. be removed by performing the following steps: Filters must be installed external to the furnace cabinet. DO NOT attempt to install filters inside the furnace. Unitary Products Group...
  • Page 7: Gas Piping

    IMPORTANT: Plan your gas supply before determining the correct gas pipe entry. Use 90-degree service elbow(s), or short nipples and con- ventional 90-degree elbow(s) to enter through the cabinet access holes. Unitary Products Group...
  • Page 8: Electrical Power

    Field wiring to the unit must be grounded. Electric wires that are field Use copper conductors only. installed shall conform to the temperature limitation for 63°F (35°C) rise wire when installed in accordance with instructions. Refer to Table 7 in these instructions for specific furnace electrical data. Unitary Products Group...
  • Page 9: Electrical Wiring

    “OFF” pins, the furnace will operate only in low The black furnace lead must be connected to the L1 (hot) wire fire. from the power supply. The white furnace lead must be connected Unitary Products Group...
  • Page 10: Thermostat Chart - Ac

    272313-UIM-A-0407 For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section. FIGURE 5: Thermostat Chart - AC Unitary Products Group...
  • Page 11: Thermostat Chart - Hp

    272313-UIM-A-0407 FIGURE 6: Thermostat Chart - HP Unitary Products Group...
  • Page 12: Accessory Connections

    Figure 8. Place the "W2 Delay" jumper in the same position of both furnace control boards. If the jumper is left in the "OFF" position, the furnaces will operate only at low fire. Unitary Products Group...
  • Page 13: Twinning Wiring Diagram - 1H/1C Thermostat

    Vent piping must be insulated with 1/2” insulation if it will be sub- jected to freezing temperatures such as routing through unheated FURNACE 1 FURNACE 2 areas or through an unused chimney. TWO-STAGE 2H/2C THERMOSTAT FIGURE 10: Twinning Wiring Diagram - 2H/2C Thermostat Unitary Products Group...
  • Page 14: Dimensions

    Dimensions are those required in Standard ASTM D-3311. NOTE: Sidewall vent terminal may be used for sidewall vent termina- tions. Refer to part list in the back of the USERS INFORMATION AND SERVICE AND MAINTENANCE MANUAL for the terminal part number. Unitary Products Group...
  • Page 15: Combustion Air Intake And Vent Connection Size At Furnace (All Models)

    Chamfer (bevel) the outer edges of the piping. clearances, and must comply with local codes and requirements. Dry-fit the vent piping assembly from the furnace to the outside ter- mination checking for proper fit support and slope. Unitary Products Group...
  • Page 16: Home Layout

    Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer. Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent. Unitary Products Group...
  • Page 17: Termination Configuration - 1 Pipe

    Under NO circumstances can the two ANTICIPATED SNOW combustion air or vent pipes be tied together. The combustion air and LEVEL OR GRADE, WHICHEVER IS vent pipes must terminate in the same atmospheric zone. HIGHER FIGURE 14: Termination Configuration - 2 Pipe Unitary Products Group...
  • Page 18: Double Horizontal Sealed Combustion Air And Vent Termination

    The second pipe (Shown in Figure 18) is the furnace vent pipe. Unitary Products Group...
  • Page 19: Outside And Ambient Combustion Air

    4. The blocking effects of louvers, grilles and screens must be given AIR (b) AIR (a) consideration in calculating free area. If the free area of a specific louver aor grille is not known. FIGURE 20: Outside and Ambient Combustion Air Unitary Products Group...
  • Page 20: Condensate Piping

    IMPORTANT: Condensate must be disposed of properly. Follow local plumbing or wastewater codes. The drain line must maintain a 1/4" per foot (0.635 cm per meter) slope to the drain. Unitary Products Group...
  • Page 21: Safety Controls

    The operation of this control indicates a malfunction in the combustion air blower, heat exchanger or a blocked vent pipe connection. Corrective action is required. These are manual reset controls that must be reset before operation can continue. Unitary Products Group...
  • Page 22 Calculate the furnace input by using one of the following equa- The induced draft blower motor will start and come up to tions. speed. Shortly after inducer start-up, the hot surface igniter will glow for about 17 seconds. Unitary Products Group...
  • Page 23 For altitudes above 2,000 ft. (610 m) the furnace input MUST BE DERATED. Refer to the GAS CONVERSION FOR PROPANE (LP) AND HIGH ALTITUDES IN SECTION IV for information on high altitude conversions. Unitary Products Group...
  • Page 24: Gas Valve

    Refer to Figure 25 for connection details. Be sure that gas valve regulator cap is in place and burner box to gas valve pressure reference hose is connected. Unitary Products Group...
  • Page 25: Reading Gas Pressure

    ADJUSTMENT JUMPER JUMPER JUMPER REMOTE BLOWER DELAY SWITCH BLUE - MED HI HI HEAT LO HEAT RED - LOW HI COOL BLACK - HI LO COOL EAC-H YELLOW - MED LOW XFMR FIGURE 26: Furnace Control Board Unitary Products Group...
  • Page 26: Furnace Control Diagnostics

    8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle. This could be caused by low gas pressure or faulty gas valve. The furnace will lock out for one hour and then restart. Unitary Products Group...
  • Page 27: Blower Performance Cfm

    1501 - 1750 42.49 - 49.55 2452 0.15 0.03736 0.14 0.03487 0.30 0.07473 1751 - 2000 49.56 - 56.63 2542 0.19 0.04733 0.18 0.04484 0.30 0.07473 2001 & Above 56.64 - Above 2987 0.19 0.04733 0.18 0.04484 0.30 0.07473 Unitary Products Group...
  • Page 28: Field Installed Accessories - Non Electrical

    17-1/2” CABINETS 1BR0121 BOTTOM RETURN FILTER KIT 1” FILTER 21” CABINETS 1BR0221 BOTTOM RETURN FILTER KIT 1-4” FILTER 21” CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1” FILTER 24-1/2” CABINETS 1BR0224 BOTTOM RETURN FILTER KIT 1-4” FILTER 24-1/2” CABINETS Unitary Products Group...
  • Page 29: Wiring Diagram

    272313-UIM-A-0407 SECTION X: WIRING DIAGRAM FIGURE 27: Wiring Diagram Unitary Products Group...
  • Page 30 272313-UIM-A-0407 NOTES Unitary Products Group...
  • Page 31 272313-UIM-A-0407 NOTES Unitary Products Group...
  • Page 32 Subject to change without notice. Printed in U.S.A. 272313-UIM-A-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 167487-UIM-B-0806 Unitary 5005 Norman Product York Group Drive 73069...