INSTALLATION MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: PS9 / FC9S / FL9S
(Single Stage Downflow/Horizontal)
40 - 120 MBH INPUT
(11.72 - 35.17 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TWINNING AND STAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Transition Kit Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Accessory Downflow Filter Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Return Filter Grill and Return Duct Installation . . . . . . . . . . . . . . . . . . . . 7
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Typical Suspended Furnace / Crawl Space Installation . . . . . . . . . . . . . 8
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Downflow Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Horizontal Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Polarity Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Heating and Cooling Thermostat Connections . . . . . . . . . . . . . . . . . . . 11
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Typical Twinned Furnace Application . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Single Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 12
Two-Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Downflow/Horizontal Vent Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
External Horizontal Vent Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Termination Configuration - 1 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . . . 4
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
High Altitude Pressure Switch Application . . . . . . . . . . . . . . . . . . . . . . . 9
High Altitude Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical and Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
(All Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.

TABLE OF CONTENTS

COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . . . . . . . . . . . .13
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .23
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
LIST OF FIGURES
Termination Configuration - 2 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Termination Configuration - 2 Pipe Horizontal . . . . . . . . . . . . . . . . . . . . 17
Crawl Space Termination Configuration - 2Pipe . . . . . . . . . . . . . . . . . . 17
Double Horizontal Sealed Combustion Air and Vent Termination . . . . . 17
Double Vertical Sealed Combustion Air and Vent Termination . . . . . . . 17
to the Burner Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Attic Combustion Air Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Condensate Drain Internal Hose Routing . . . . . . . . . . . . . . . . . . . . . . . 20
Downflow Condensate Drain Hose Configuration . . . . . . . . . . . . . . . . . 20
Pressure Switch Tubing Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Typical Heat/Cool Speed Tap Connections . . . . . . . . . . . . . . . . . . . . . . 27
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
LIST OF TABLES
Combustion Air Supply and Vent Piping . . . . . . . . . . . . . . . . . . . . . . . . 14
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . . . . 18
Condensate Drain Hose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Blower Performance CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
035-20646-001 Rev. A (1004)

Advertisement

Table of Contents
loading

Summary of Contents for Unitary products group PS9

  • Page 1: Table Of Contents

    INSTALLATION MANUAL HIGH EFFICIENCY EFFICIENCY RATING CERTIFIED TUBULAR HEAT EXCHANGER SERIES MODELS: PS9 / FC9S / FL9S (Single Stage Downflow/Horizontal) 40 - 120 MBH INPUT This product was manufactured in a plant whose quality system is certified/registered as being (11.72 - 35.17 KW) INPUT in conformity with ISO 9001.
  • Page 2: Safety

    When outdoor air is used for combustion, the combustion air intake pipe allowed for both the burners and blower. termination must be located external to the building and in an area where there will be no exposure to the substances listed above. Unitary Products Group...
  • Page 3 2. Minimum of 8” clearance required to install condensate removal system. 3. Line contact only permitted between lines formed by the intersection of the rear panel (top in horizontal position) of the furnace jacket and building joists, studs or framing. Unitary Products Group...
  • Page 4: Ductwork

    The External Static Pressure is determined by adding the Supply removed and a new plenum installed that is the proper size for the new Duct Static Pressure reading to the Return Duct Static Pressure furnace. reading. Unitary Products Group...
  • Page 5 Refer to the installation instructions supplied with the air conditioning cabinet by the use of screws and then it must be sealed to prevent coil for additional information. leaks. Unitary Products Group...
  • Page 6 S cleat material when a metal plenum is used. IMPORTANT: If an external mounted filter rack is being used see the The use of an approved flexible duct connector is recommended on all instructions provided with that accessory for proper hole cut size. Unitary Products Group...
  • Page 7: Filters

    The use of straps and / or sup- cleaner. ports is required to support the weight of the external filter box. An accessory filter rack is available. Refer to Figure 4 and the instruc- tions supplied with the furnace accessory external filter kit options. Unitary Products Group...
  • Page 8: Gas Piping

    ROD & FURNACE 6” MIN. BETWEEN 1” MAX. BETWEEN the rating plate. ROD & FURNACE ROD & FURNACE FIGURE 7: Typical Suspended Furnace / Crawl Space Installation Unitary Products Group...
  • Page 9: High Altitude Pressure Switch Application

    A wrench must be placed on the octa- Natural gon hub located on the gas inlet side of the valve. Placing a wrench Propane to the body of the gas valve will damage the valve causing improper operation and/or the valve to leak. Unitary Products Group...
  • Page 10: Electrical Power

    L1 (hot) wire from the power supply. The white furnace lead must be connected to neutral. Connect the green fur- FIGURE 11: Electrical Wiring nace lead (equipment ground) to the power supply ground. An Unitary Products Group...
  • Page 11: Accessory Connections

    If a mixing device is not used, any ducts that are connected down stream from the furnace that operates on W2, will be supplying cold air in the Heating mode to the FIGURE 14: Accessory Connections occupied spaces unless W2 is energized. Unitary Products Group...
  • Page 12: Typical Twinned Furnace Application

    The twinning control ensures that both blowers come on and shut off at the same time. Unitary Products Group...
  • Page 13: Combustion Air Intake And Vent Connection Size At Furnace (All Models)

    3” (7.62 cm). or vent connector, and not connected to any portion of a factory- built or masonry chimney The furnace shall not be connected to a chimney flue serving a sep- arate appliance designed to burn solid fuel. Unitary Products Group...
  • Page 14: Combustion Air Supply And Vent Piping

    COMBUSTION AIR / VENT CLEARANCES side termination. Ventilated combustion air systems from the furnace to the IMPORTANT: The vent must be installed with the following minimum attic or crawl space termination. clearances, and must comply with local codes and requirements. Unitary Products Group...
  • Page 15: Home Layout

    Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer. Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent. Unitary Products Group...
  • Page 16: Downflow/Horizontal Vent Assembly

    2” PVC 2” PVC LEVEL. MAXIMUM 24” ABOVE ROOF. 45° STELL FURNACE HORIZONTAL LEFT VENT PIPE 12” MIN. 12” MIN. DOWNFLOW RETURN BARBED FITTING HORIZONTAL RIGHT FIGURE 19: Downflow/Horizontal Vent Assembly FIGURE 21: Termination Configuration - 1 Pipe Unitary Products Group...
  • Page 17: Termination Configuration - 2 Pipe

    The vent system may be supported terminate in the attic. The vent must terminate outside. by the use of clamps or hangers secured to a permanent part of the structure every 4 ft. (1.22 m). Unitary Products Group...
  • Page 18: Sealed Combustion Air Intake Connection And Vent Connection

    The following must be considered to obtain proper air for combus- 120,000 750 (1905 cm tion and ventilation in confined spaces. EXAMPLE: Square feet is based on 8 foot ceilings. 28,000 BTUH X 50 Cubic Ft. = 1,400 = 175 Sq. Ft. 1,000 8’ Ceiling Height Unitary Products Group...
  • Page 19: Outside And Ambient Combustion Air

    NOTE: An unsafe condition exists when the CO reading exceeds 40 ppm and the draft reading is not in excess of - 0.1 in. W.C. (-25 kPa) with all of the appliance(s) operating at the same time. FIGURE 30: Attic Combustion Air Termination Unitary Products Group...
  • Page 20: Condensate Piping

    HOSE #5 HOSE #1 2-3/4” HOSE #1 3/4” 3/4” SPRING CLAMP HOSE #3 DOGLEG 9” 8-1/8” 2” 5/8” 3/4” SPRING CLAMP SPRING CLAMP 1-1/8” HOSE #3 HOSE #4 1/2” 3-3/8” FIGURE 32: Downflow Condensate Drain Hose Configuration Unitary Products Group...
  • Page 21: Horizontal Left Condensate Drain Hose Configuration

    Remove the large condensate cap from the side of the condensate pan, close to the knockout, and install it on the middle of the con- densate pan, from where hose #1 was removed. Unitary Products Group...
  • Page 22: Horizontal Right Condensate Drain Hose Configuration

    THIS TUBE FOR THE 4-1/2” BLOCKED CONDENSATE PIECE HOSE #7 SWITCH HAS BEEN HOSE #2 DOGLEG FACTORY INSTALLED FOR THIS POSITION. 8-1/8” RECOMMENDED HOSE #9 3/4” 1-5/8” CONDENSATE TRAP ORIENTATION 3/4” 33” FIGURE 34: Horizontal Right Condensate Drain Hose Configuration Unitary Products Group...
  • Page 23: Safety Controls

    Be sure proper ventilation is available to dilute and carry away any vented gas. Unitary Products Group...
  • Page 24 Calculate the furnace input by using one of the following equa- System start-up will occur as follows: tions. The induced draft blower motor will start and come up to speed. Shortly after inducer start-up, the hot surface igniter will glow for about 17 seconds. Unitary Products Group...
  • Page 25 For altitudes above 2,000 ft. (610 m) the furnace input MUST BE DERATED. Refer to the GAS CONVERSION FOR PROPANE (LP) AND HIGH ALTITUDES IN SECTION IV for information on high altitude conversions. Unitary Products Group...
  • Page 26: Gas Valve

    Refer to Figure 36 for connection details. sooting and eventual clogging of the heat exchanger could occur. Be sure that gas valve regulator cap is in place and burner box to gas valve pressure reference hose is connected. Unitary Products Group...
  • Page 27: Reading Gas Pressure

    FAN OFF ADJUSTMENT connected to the desired motor lead. Place all unused motor leads on JUMPER Park terminals. Two are provided. Y1 Y/Y2 W FIGURE 38: Typical Heat/Cool Speed Tap Connections Unitary Products Group...
  • Page 28: Filter Performance - Pressure Drop Inches W.c. And (Kpa)

    1751 - 2000 49.56 - 56.63 965.2 0.19 0.04733 0.18 0.04484 0.30 0.07473 2001 & Above 56.64 - Above 1176.0 0.19 0.04733 0.18 0.04484 0.30 0.07473 1. Washable Fibers are the type supplied with furnace (if supplied). Unitary Products Group...
  • Page 29 HIGH ALTITUDE PRESSURE SWITCH KIT FOR APPLICATION INFORMA- 1PS0902 (Does Not Include Orifices) TION SEE FORM 035-14447-000 1PS0903 1NK0301 CONDENSATE NEUTRALIZER KIT ALL MODELS 1TK0917 17 1/2” CABINETS 1TK0921 TRANSITION KITS FOR COIL MOUNTING 21” CABINETS 1TK0924 24 1/2” CABINETS Unitary Products Group...
  • Page 30: Wiring Diagram

    035-20646-001 Rev. A (1004) SECTION XII: WIRING DIAGRAM FIGURE 39: Wiring Diagram Unitary Products Group...
  • Page 31 035-20646-001 Rev. A (1004) NOTES Unitary Products Group...
  • Page 32 NOTES Subject to change without notice. Printed in U.S.A. 035-20646-001 Rev. A (1004) Copyright © by York International Corp. 2004. All rights reserved. Supersedes: Nothing Unitary 5005 Norman Product York Group Drive 73069...

This manual is also suitable for:

Fc9sFl9s

Table of Contents