USER'S INFORMATION,

MAINTENANCE AND
SERVICE MANUAL
MODELS: 90% P*DH / G9T-DH / FG9-DH (Downflow)
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
USER'S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . . 3
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . . 3
Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . . 5
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

CONTACT INFORMATION

• Go to website at www.york.com click on "contact", then click on "contact form" and follow the instructions.
• Contact us by mail:
The manufacturer recommends that the user read all sec-
tions of this manual and keep the manual for future refer-
ence.
FIRE OR EXPLOSION HAZARD - Failure to follow
safety warnings exactly could result in serious injury,
death, or property damage.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone (including cell phone) in your building.
Leave the building immediately.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas sup-
plier.

TABLE OF CONTENTS

FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .5
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Continuous Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Intermittent Blower - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Secondary Heat Exchanger . . . . . . . . . . . . . . . . . . .6
Cleaning the Vent / Air Intake System . . . . . . . . . . . . . . . . . . . . . .6
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .6
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .10
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
York International Corperation
Consumer Relations
5005 York Drive
Norman, OK 73069
SECTION I: USER'S INFORMATION

SAFETY

1.
The furnace area must be kept clear and free of combustible mate-
rials, gasoline and other flammable vapors and liquids.
2.
Insulating materials may be combustible. The furnace must be
kept free and clear of insulating materials. The furnace area must
be examined when installed in an attic or other insulated space or
when insulation is added to be sure that the insulation material has
been kept away from the furnace.
3.
The furnace needs air for combustion in order to operate properly
and safely. Do not block or obstruct air openings on the furnace,
air openings to the area where the furnace is installed, or spaces
around the furnace.
4.
Follow the instructions exactly as shown on the OPERATING
INSTRUCTION LABEL or the Start-up and Shutdown Instructions
on Page 3 of this manual when lighting the furnace or turning the
furnace off.
5.
Should the gas supply fail to shut off or if overheating occurs, shut
off the gas valve to the furnace before shutting off the electrical
supply.
6.
Do not use this furnace if any part has been under water. A flood-
damaged furnace is extremely dangerous. Attempts to use the fur-
nace can result in fire or explosion. A qualified service agency
should be contacted to inspect the furnace and replace all gas
controls, control system parts, electrical parts that have been wet
or the furnace if deemed necessary.
EFFICIENCY
RATING
CERTIFIED
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
035-19600-001 Rev. B (0204)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 90% P DH and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group 90% P DH

  • Page 1: Table Of Contents

    USER’S INFORMATION, EFFICIENCY MAINTENANCE AND RATING CERTIFIED SERVICE MANUAL This product was manufactured in a plant whose quality system is certified/registered as being in conformity with ISO 9001. MODELS: 90% P*DH / G9T-DH / FG9-DH (Downflow) TABLE OF CONTENTS CONTACT INFORMATION ....... . 1 FURNACE MAINTENANCE SECTION .
  • Page 2: Instructions For Examining The Furnace Installation

    EXAMINE VENT PIPE EXAMINE EXAMINE REMOVE THIS FURNACE PANEL TO FURNACE PLACE A FIELD CASING CASING EXAMINE THE INSTALLED ACCESS BURNER FLAMES PANEL LOCATED IN THE DOWNFLOW PLENUM TO EXAMINE THE HEAT EXCHANGER FIGURE 3: Furnace Examination Checkpoints Unitary Products Group...
  • Page 3: How Your Gas Furnace Works

    “TO TURN OFF THE APPLIANCE” and call supplies to the furnace. Check all metal parts and surfaces your service technician or gas supplier. to be sure they have cooled to room temperature before you begin. Unitary Products Group...
  • Page 4: Blower Care

    The motors in these furnaces are permanently lubricated, and do not require periodic oiling. NOTE: FILTER ACCESS THRU DUCTWORK MUST BE PROVIDED BRANCH FOR REMOVAL AND CLEANING DUCTS FILTERS FILTER RACK DUCTWORK CROSS SECTION A-A (WITH PLENUM AND FILTERS) FIGURE 6: Filter Rack Assembly and Attachment Unitary Products Group...
  • Page 5: Service And Maintenance Manual

    If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries. Unitary Products Group...
  • Page 6: Hot Surface Ignition System

    Clean - vacuum all burners. Never adjust pressure switch to allow furnace operation. Replace all components in reverse order. Reconnect all wiring. Restore electrical power and gas supply to the furnace. Check furnace operation. Follow operating instructions. Unitary Products Group...
  • Page 7 Thermostat Calling for Heat (Seconds) Fan on Delay 30 Seconds THERMOSTAT INDUCER 15 Sec. Post Purge IGNITOR MAIN VALVE HUMIDIFIER ELECTRONIC AIR CLEANER CIRCULATING BLOWER 60, 90, 120, 180 SEC. Selectable Fan Off Delay FIGURE 8: Furnace Control Event Schedule Unitary Products Group...
  • Page 8: Replacement Parts List

    035-19600-001 Rev. B (0204) SECTION III: REPLACEMENT PARTS LIST Unitary Products Group...
  • Page 9 PANEL, FRONT (Blower) PANEL, FRONT (Burner) NOTE: *Not Shown New replacement parts shown in bold face type at the first printing of parts list dated 11/02. Major components and suggested stocking items are shown with shaded item number. Unitary Products Group...
  • Page 10: Field Installed Accessories - Non-Electrical

    Click on the “Brand Links” button b. Click on the “Customer Service” button • You can contact us by mail. Just send a written request to: York International Consumer Relations 5005 York Drive Norman, OK 73069 Unitary Products Group...
  • Page 11: Wiring Diagram

    035-19600-001 Rev. B (0204) SECTION IV: WIRING DIAGRAM FIGURE 9: Wiring Diagram Unitary Products Group...
  • Page 12: Limited Warranty

    PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________ UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________ Subject to change without notice. Printed in U.S.A. 035-19600-001 Rev. B (0204) Copyright © by Unitary Products Group 2004. All rights reserved. Supersedes: 035-19600-001 Rev. A (1103) Unitary 5005...

This manual is also suitable for:

Fg9-dhG9t-dh

Table of Contents